1 Supplementary Operating Manual
7 of 28
Profibus module
1.5 Connecting the field bus module
For connecting the field bus module observe the installation guide of the Profibus
user organisation (PNO) (download from "
http://www.profibus.com/download/
"). Pay particular attention to the following:
▪
Before the bus connection is established among the nodes, potential equalisation
must have been implemented and checked.
▪
For high-frequency shielding, use shielded cables and assemble according to EMC
requirements.
▪
A minimum distance of 0.3 metres is recommended between such cables and
other electric conductors.
▪
Do not use the bus cable to make any further connections in addition to the field
bus module (for example, 230 V alert and 24 V start).
▪
A cable specified for the field bus module must be used as the connecting cable.
CAUTION
Incorrect installation
Damage to the field bus module!
▷
Never supply power to the field bus module via the M12 connections.
B
A
B
A
2
1
Fig. 5:
Connecting the field bus module
Table 3:
Connecting the field bus module
Item
Device
M12 connector
1
Frequency inverter 1
M12 connector A: Coming
M12 socket B: Going
2
Frequency inverter 2
M12 connector A: Coming
M12 socket B: Going