1 Supplementary Operating Manual
21 of 28
Profibus module
Table 9:
Rotodynamic Pump module, output
Offset Byte.Bit
Data type
Parameter
name
Functional
element
Description
Unit
0.7
BOOL
PUMP_KICK_REQ
PumpKick.VALUE
0 => 1 starts a functional check run
-
0.4
BOOL
REMOTE_OPERATION -
Not supported
-
0.3
BOOL
DIRECTION_REQ
-
Not supported
-
0.2
BOOL
RESET_FAULT
GenericPump.RESET_
FAULT
0 => 1 acknowledges warnings and alerts and
clears the fault
-
0.1
BOOL
ON_OFF_REQ
GenericPump.ON_OF
F
1: Pump ON
-
0.0
BOOL
REMOTE_ACCESS_RE
QUEST
GenericPump.REMOT
E_ACCESS_REQUEST
-
-
1
BYTE
CONTROL_MODE
PumpActuation.CON
TROL_MODE
128: OFF (control system OFF, fixed speed
operation)
-
129: Discharge pressure
-
130: Suction pressure
-
131: Differential pressure
-
132: Differential pressure (sensorless)
-
133: Flow rate
-
134: Flow rate (sensorless)
-
135: Temperature (cooling)
-
136: Temperature (heating)
-
137: Suction-side level
-
138: Discharge-side level
-
2
BYTE
OPERATION_MODE
PumpActuation.OPE
RATION_MODE
Request of operating mode:
128: Off
-
129: Manual mode
-
130: Automatic mode
-
3
INT16
SETPOINT
PumpActuation.SETP
OINT
Setpoint of the corresponding type of control
(CB_CONTROL_MODE). The value range
corresponds to that of the process value
(actual value).
0,01 %
NOTE
In order for the PLC to be able to write data from the “Rotodynamic Pump,
Output” area to the frequency inverter, it must be ensured that “Remote Request
Access” is set. This bit can remain permanently set. The data can only be written
when “Bit 0 - Access Mode” is confirmed at the PLC. This bit is flank-controlled and
must therefore be set again after, for example, a power failure. This likewise
applies to the bytes “Byte 1 - Control Mode” and “Byte 2 - Operation Mode”.
1.7.3 Definition of the feedback module available in the cyclic data exchange
The feedback module is required for transmitting an actual value for the closed-loop
control of PumpDrive 2 via field bus. In this case process control is effected by
PumpDrive 2.
Table 10:
Feedback module, output
Module designation
Data type
Description
Menu
Unit
Functional element
Feedback/ VALUE
INT
Actual value
(closed-loop
control)
1-2-3-1
0,01 %
Feedback.VALUE