1 Supplementary Operating Manual
22 of 28
Profibus module
1.7.4 Definition of the modules for reading out process values available in the cyclic
data exchange
Each process value is represented by the corresponding module. All process values are
of the REAL data type.
Table 11:
Process value modules, input
Module designation
Data type
Description
Menu
Unit
Functional element
DiffPressure/VALUE
REAL
Process value
differential
pressure
1-2-3-4
bar
DiffPressure.VALUE
FlowVelocity/VALUE
REAL
Flow velocity
1-2-3-8
m/s
FlowVelocity.VALUE
Frequency/VALUE
REAL
Output frequency
1-2-1-7
Hz
Frequency.VALUE
Head/VALUE
REAL
Head
1-2-3-9
m/s
Head.VALUE
InletPressure/VALUE
REAL
Suction pressure
1-2-3-2
bar
InletPressure.VALUE
Level/VALUE
REAL
Fill level
1-2-3-6
m/s
Level.VALUE
MotorVoltage/VALUE
REAL
Motor voltage
1-2-1-6
V
MotorVoltage.VALUE
OutletPressure/VALUE
REAL
Discharge pressure 1-2-3-3
bar
OutletPressure.VALUE
Power/VALUE
REAL
Motor input power 1-2-1-2
kW
Power.VALUE
PowerElectronicTemp/
VALUE
REAL
Heat sink
temperature
1-2-1-9
°C
PowerElectronicTemp.VA
LUE
PumpLiquidTemp/VALUE REAL
Temperature
1-2-3-7
°C
PumpLiquidTemp.VALUE
Speed/VALUE
REAL
Speed
1-2-1-1
rpm
Speed.VALUE
Torque/Value
REAL
Motor torque
1-2-1-11
Nm
Torque.Value
VolumeFlow/VALUE
REAL
Flow rate
1-2-3-5
m³/h
VolumeFlow.VALUE
MotorCurrent/VALUE
REAL
Motor current
1-2-1-5
A
MotorCurrent.VALUE
1.7.5 Contents of the diagnosis modules available in the cyclic data exchange
Description of the diagnosis parameters supported in the PumpDrive 2 Profibus
implementation by the corresponding messages.
Table 12:
Module PB/DIAGNOSIS (PhysicalBlock.DIAGNOSIS), input
Offset byte.
Bit
Data type
Error code
Parameter
name
Comments
PumpDrive 2
message
0.0-0.7 BOOL
0x9000-0x9007 -
Reserved by PI, fixed at 0
-
1.0-1.2 BOOL
0x9008-0x900A -
Reserved by PI, fixed at 0
-
1.3
BOOL
0x900B
DIA_WARMSTART
Reserved by PI, not a PIP component, fixed at
0
-
1.4
BOOL
0x900C
DIA_COLDSTART
Reserved by PI, not a PIP component, fixed at
0
-
1.5
BOOL
0x900D
DIA_MAINTENANCE
1: Active maintenance interval of the pump
I100
1.6
BOOL
0x900E
-
Reserved by PI, fixed at 0
-
1.7-2.3 BOOL
0x900F-0x9013
IDENT_NUMBER_VIO
LATION
Not supported
-
2.4-2.7 BOOL
0x9014-0x9017 -
Reserved by PI, fixed at 0
-
3.0
BOOL
0x9018
DIA_HARDWARE
Hardware diagnosis event
-
3.1
BOOL
0x9019
DIA_SOFTWARE
Software diagnosis event
-
3.2
BOOL
0x901A
DIA_MECHANICS
Mechanics diagnosis event
-
3.3
BOOL
0x901B
DIA_ELETRICS
Electrics diagnosis event
-
3.4
BOOL
0x901C
DIA_PROCESS
Process diagnosis event
-
3.5
BOOL
0x901D
DIA_OPERATION
Operation diagnosis event
-