KSB Profibus PumpDrive 2 Supplementary Operating Manual Download Page 25

1 Supplementary Operating Manual

25 of 28

Profibus module

Table 18: 

PB/DIAGNOSIS_EXT_OPERATION (PhysicalBlock.DIAGNOSIS_EXT_OPERATION), input

Offset byte.

Bit

Data type

Error code

Parameter

name

Comments

PumpDrive 2

message

0.0-3.0 BOOL

0x9701-0x9719 -

Not supported

-

3.1

BOOL

0x971A

OverLoad

Overload

W58

3.2

BOOL

0x971B

PartialLoad

Part load

W57

3.3-4.0 BOOL

0x971C-0x9721 -

Not supported

-

4.1

BOOL

0x9722

DriveOverheat

Heat sink temperature high

A7, W59

4.2

BOOL

0x9723

MotorOverheat

Thermal motor protection

A1

4.3

BOOL

0x9724

ContrOverheat

PCB temperature high

A8, W60

4.4

BOOL

0x9725

-

Not supported

-

4.5-4.6 BOOL

0x9700,
0x9726-0x977F

-

Reserved by PI, fixed at 0

-

4.7

BOOL

0x9780-0x978F

Make-specific

No master control

A16

External message

A30, W30

Resonance range

W53

Actual value failure

W55

Speed monitoring

W63

Setpoint monitoring

W64

Actual value monitoring

W65

Flow rate monitoring

W66

Suction pressure monitoring

W67

Discharge pressure monitoring

W68

Differential pressure monitoring

W69

Temperature monitoring

W70

Low flow velocity

W80

Pipe flushing mode active

I102

Pipe filling mode active

I103

Overflow

W83

Table 19: 

PB/DIAGNOSIS_EXT_AUX_DEVICE (PhysicalBlock.DIAGNOSIS_EXT_AUX_DEVICE), input

Offset byte.

Bit

Data type

Error code

Parameter

name

Comments

PumpDrive 2

message

0.0

BOOL

0x9A01

AuxDeviceFault

Not supported

-

0.1

BOOL

0x9A02

SensorElement

Broken wire

W54

0.2-4.2 BOOL

0x9A03-0x9A23 -

Not supported

-

4.3

BOOL

0x9A24

-

Not defined

-

4.4-4.6 BOOL

0x9A00,
0x9A25-0x9A7F

-

Reserved by PI, fixed at 0

-

4.7

BOOL

0x9A80, 0x9A81 Make-specific

PumpMeter communication

W77

Summary of Contents for Profibus PumpDrive 2

Page 1: ...Field Bus Module Profibus module PumpDrive 2 Supplementary Operating Manual...

Page 2: ...ontents provided herein must neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without the manuf...

Page 3: ...quency inverter operation with Profibus module 10 1 7 1 Addressing the parameters defined in the PIP for access via MS1 11 1 7 2 Definition of the rotodynamic pump module available in the cyclic data...

Page 4: ...cification Configuration is done via frequency inverter parameters Communication protocol Profibus DP Bus terminator External Interface EIA 485 RS485 Transmission rate Automatic 9600 12 Mbit s Device...

Page 5: ...artbeat detected 4 Green LED signal lamp Communication on field bus side active possible 5 Red LED signal lamp Profibus fault or communication error Can be retrofitted Internal T connector bus looped...

Page 6: ...ield bus module into the open slot The plug in module is guided on rails until it engages in the contact Fig 4 Securing the field bus module 2 Secure the field bus module using the 4 cross recessed he...

Page 7: ...C requirements A minimum distance of 0 3 metres is recommended between such cables and other electric conductors Do not use the bus cable to make any further connections in addition to the field bus m...

Page 8: ...for Profibus 4 Further Profibus nodes b a 2 1 5 3 4 1 5 4 3 2 Fig 7 Pin assignment a Contact arrangement of M12 connector b Contact arrangement of M12 socket Table 4 Pin assignment Pin Core colour co...

Page 9: ...it must be implemented externally using an active bus terminator NOTE The frequency inverter is reset when a field bus module is replaced or retrofitted Menu 3 12 for setting the parameters of the fie...

Page 10: ...to actual value failure 0 0 10 0 1 NOTE If the field bus is only used for monitoring purposes the Control Point parameter 3 6 2 is set to Local NOTE If the cycle times of parameters 3 12 1 3 and 3 12...

Page 11: ...by indicating the corresponding menu number if available and the valid value range for the parameters The operating values are indicated in the unit shown under Values It corresponds with the four di...

Page 12: ...nericPump 2 17 PUMP_TYPE_ID 1 r Unsigned8 1 Pump type ID 3 to PIP specification 3 11 18 PUMP_TYPE_VERS 2 r Unsigned8 1 1 to PIP specification 1 12 19 ON_OFF 3 rw Boolean 1 System start stop 1 3 1 FALS...

Page 13: ...2 3 1 0 100 of the value range defined for the process variable 0 20 25 FEEDBACK_UNIT 9 rw Unsigned16 2 1342 21 28 OPERATION_MODE 12 rw Unsigned8 1 Operating mode 1 3 8 128 Off 129 Manual mode 130 Au...

Page 14: ...1 28 21 PUMP_COLLECTIVE _IDS 5 r Unsigned8 1 0 0 29 22 MAX_NUM_PUMP_ OPERATION 6 rw Unsigned8 1 Maximum number of pumps running 3 7 2 1 6 1 30 24 EXCHANGE_EVENT 8 rw Boolean 1 Immediate pump changeov...

Page 15: ...imum speed FALSE Pump does not run at maximum motor speed TRUE Pump runs at maximum motor speed 3 2 2 2 FALSE 41 11 PumpSpeedMin 10 17 VALUE 1 r Boolean 1 Operation at minimum speed FALSE Pump does no...

Page 16: ...d16 2 Hz 1077 61 33 Torque 21 17 VALUE 1 r Float32 4 Motor torque 1 2 1 11 0 62 18 VALUE_UNIT 2 r Unsigned16 2 Nm 1136 63 34 PumpLiquidTemp 22 17 VALUE 1 r Float32 4 Temperature 1 2 3 7 200 64 18 VALU...

Page 17: ...late 0 480 V 400 84 21 CURRENT 5 r Float32 4 Nominal motor current 3 2 1 4 Motor name plate 0 150 A 2 6 85 23 POWER 7 r Float32 4 Nominal motor power 3 2 1 1 Motor name plate 0 55 kW 7 86 25 FREQUENCY...

Page 18: ...ve 2 50 C 50 94 26 TEMP_LOW 10 r Float32 4 Minimum in service ambient temperature Technical data PumpDrive 2 10 C 10 95 28 VOLTAGE_MAX 12 r Float32 4 Maximum rated voltage Name plate PumpDrive 2 400 V...

Page 19: ...module contains bit variables byte variables and word variables This does not apply to the process variable view A process image is not required as byte operations word operations or double word oper...

Page 20: ...OL_MODE PumpActuation CB_C ONTROL_MODE 132 Differential pressure sensorless 133 Flow rate 134 Flow rate sensorless 135 Temperature cooling 136 Temperature heating 137 Suction side level 138 Discharge...

Page 21: ...uest of operating mode 128 Off 129 Manual mode 130 Automatic mode 3 INT16 SETPOINT PumpActuation SETP OINT Setpoint of the corresponding type of control CB_CONTROL_MODE The value range corresponds to...

Page 22: ...m Speed VALUE Torque Value REAL Motor torque 1 2 1 11 Nm Torque Value VolumeFlow VALUE REAL Flow rate 1 2 3 5 m h VolumeFlow VALUE MotorCurrent VALUE REAL Motor current 1 2 1 5 A MotorCurrent VALUE 1...

Page 23: ...hardware test not passed A98 IO hardware test not passed A99 24 V overload W76 Table 14 Module PB DIAGNOSIS_EXT_SOFTWARE PhysicalBlock DIAGNOSIS_EXT_SOFTWARE input Offset byte Bit Data type Error code...

Page 24: ...VoltageInDevice Not supported 1 5 BOOL 0x940E CurrentInDevice Overcurrent A9 1 6 BOOL 0x940F ShortToEarth Not supported 1 7 BOOL 0x9410 ShortCircuit Short circuit A5 2 0 BOOL 0x9411 WindingTemp Not s...

Page 25: ...ke specific No master control A16 External message A30 W30 Resonance range W53 Actual value failure W55 Speed monitoring W63 Setpoint monitoring W64 Actual value monitoring W65 Flow rate monitoring W6...

Page 26: ......

Page 27: ......

Page 28: ...KSB SE Co KGaA Johann Klein Stra e 9 67227 Frankenthal Germany Tel 49 6233 86 0 www ksb com 4074 801 05 EN 01505510...

Reviews: