1 Supplementary Operating Manual
Profibus module
17
of
28
ID functional element
Functional element
Slot
Index
Parameter name
Rel Index
Access
(r: read, w: write)
Data type
Size [byte]
Description
KSB menu number
Value range
Value (example)
Parameter index
56
Energy
29
17
VALUE
1
r
Float32
4
Energy meter
(kWh)
1-4-1-1
-
0
78
18
VALUE_UNIT
2
r
Unsigned16 2
-
-
kWh
1179
79
60
OperationTime
30
17
VALUE
1
r
Float32
4
Pump operating
hours
1-4-2-3
-
555
80
18
VALUE_UNIT
2
r
Unsigned16 2
-
-
h
1059
81
61
TotalPoweredTime 31
17
VALUE
1
r
Float32
4
Frequency inverter
operating hours
1-4-2-1
-
1965
82
18
VALUE_UNIT
2
r
Unsigned16 2
-
-
h
1059
83
65
Motor
32
19
VOLTAGE
3
r
Float32
4
Nominal motor
voltage
3-2-1-2
Motor name plate 0..480 V
400
84
21
CURRENT
5
r
Float32
4
Nominal motor
current
3-2-1-4
Motor name plate 0..150 A
2,6
85
23
POWER
7
r
Float32
4
Nominal motor
power
3-2-1-1
Motor name plate 0..55 kW
7
86
25
FREQUENCY
9
r
Float32
4
Nominal motor
frequency
3-2-1-3
Motor name plate 0..100 Hz
50
87
28
ROTOR_SPEED
12 r
Float32
4
Nominal motor
speed
3-2-1-5
Motor name plate 0..4200 rpm
1500
88
29
MAX_ROTOR_SPEE
D
13 r
Float32
4
Maximum motor
speed
3-2-2-2
Motor name plate 0..4200 rpm
1500
89
66
Converter
33
19
SUPPLY_VOLTAGE_
HIGH
3
r
Float32
4
Maximum nominal
voltage
-
Technical data PumpDrive 2
480 V
480
90
20
SUPPLY_VOLTAGE_
LOW
4
r
Float32
4
Minimum mains
voltage
-
Technical data PumpDrive 2
380 V
380
91
22
SUPPLY_FREQUENC
Y_HIGH
6
r
Float32
4
Maximum mains
frequency
-
Technical data PumpDrive 2
60 Hz
60
92
23
SUPPLY_FREQUENC
Y_LOW
7
r
Float32
4
Minimum mains
frequency
-
Technical data PumpDrive 2
50 Hz
50