1 Supplementary Operating Manual
Profibus module
13
of
28
ID functional element
Functional element
Slot
Index
Parameter name
Rel Index
Access
(r: read, w: write)
Data type
Size [byte]
Description
KSB menu number
Value range
Value (example)
Parameter index
3
PumpActuation
3
17
SETPOINT
1
rw
Float32
4
Setpoint (closed-
loop control) /
Control value
(open-loop control)
1-3-2,
1-3-3
0-100 % of the value range
defined for the process variable
0
18
19
SETPOINT_UNIT
3
r
Unsigned16 2
-
%
1342
19
23
FEEDBACK
7
rw
Float32
4
Actual value
(closed-loop
control)
1-2-1,
1-2-3-1
0-100 % of the value range
defined for the process variable
0
20
25
FEEDBACK_UNIT
9
rw
Unsigned16 2
-
%
1342
21
28
OPERATION_MODE 12 rw
Unsigned8
1
Operating mode
1-3-8
128: Off
129: Manual mode
130: Automatic mode
130
22
29
CB_OPERATION_M
ODE
13 r
Unsigned8
1
Status: operating
mode
1-3-8
See: Operating mode
130
23
31
CONTROL_MODE
15 rw
Unsigned8
1
Type of control
3-6-1
128: Off (open-loop control)
129: Discharge pressure
130: Suction pressure
131: Differential pressure
132: Differential pressure
(sensorless)
133: Flow rate
134: Flow rate (sensorless)
135: Temperature (cooling)
136:Temperature (heating)
137: Suction-side level
138: Discharge-side level
128
24
32
CB_CONTROL_MO
DE
16 r
Unsigned8
1
Status: type of
control
3-6-1
See: Type of control
128
25
Summary of Contents for Profibus PumpDrive 2