5 Installation at Site
29 of 96
Magnochem-Bloc
Soft starting
Soft starting a motor means that only the voltage level is changed and not the
frequency as it is the case with frequency inverter starting.
Soft starter settings:
▪
Starting voltage: 40 %
▪
Run-up time 10 seconds for voltage-controlled run-up
Table 9:
Selection table for suitable starting methods
Information specified in data sheet
✘
= Suitable,
○
= Not suitable
Permissible starting method
DOL starting
Star-delta
starting
Starting via frequency
inverter
Soft starting
Magnetic coupling selected for DOL
starting
✘
○
✘
✘
Magnetic coupling selected for star-delta
starting
✘
✘
✘
✘
Magnetic coupling selected for
frequency inverter starting
○
○
✘
○
Magnetic coupling selected for soft
starting
○
○
✘
✘
1. Check the available mains voltage against the data on the motor name plate.
CAUTION
Incorrect starting method without taking the selected magnetic coupling into
account
Damage to the pump (set)!
▷
Observe the information provided in the data sheet.
2. Select a suitable starting method (see selection table for suitable starting
methods).
DANGER
Excessive motor surface temperature
Explosion hazard!
Damage to the motor!
▷
Check the suitability of the frequency inverter/soft starter fitted to the motor.
▷
Adjust the motor design data at the frequency inverter/soft starter.
3. Adjust the motor design data at the frequency inverter/soft starter if required.
NOTE
A motor protection device is recommended.
5.6.1 Earthing
DANGER
Electrostatic charging
Explosion hazard!
Damage to the pump set!
▷
Connect the PE conductor to the earthing terminal provided.
▷
Provide for potential equalisation between the pump set and foundation.