6 Commissioning/Start-up/Shutdown
37 of 78
Etanorm-R
1222.8/13-EN
6.1.5 Start-up
DANGER
Non-compliance with the permissible pressure and temperature limits if the pump
is operated with the suction and/or discharge line closed.
Explosion hazard!
Hot or toxic fluids escaping!
▷
Never operate the pump with the shut-off elements in the suction line and/or
discharge line closed.
▷
Only start up the pump set with the discharge-side shut-off element slightly or
fully open.
DANGER
Excessive temperatures due to dry running or excessive gas content in the fluid
handled
Explosion hazard!
Damage to the pump set!
▷
Never operate the pump set without liquid fill.
▷
Prime the pump as per operating instructions. (
▷
Always operate the pump within the permissible operating range.
CAUTION
Abnormal noises, vibrations, temperatures or leakage
Damage to the pump!
▷
Switch off the pump (set) immediately.
▷
Eliminate the causes before returning the pump set to service.
ü
The system piping has been cleaned.
ü
The pump, suction line and inlet tank, if any, have been vented and primed with
the fluid to be handled.
ü
The lines for priming and venting have been closed.
CAUTION
Start-up against open discharge line
Motor overload!
▷
Make sure the motor has sufficient power reserves.
▷
Use a soft starter.
▷
Use speed control.
1. Fully open the shut-off element in the suction head/suction lift line.
2. Close or slightly open the shut-off element in the discharge line.
3. Start up the motor.