The tables that follow are applicable in these conditions:
•
Device installation must agree with the instructions given in the handbook.
•
Make sure that the device temperature does not increase because of other heat sources
(sunlight, adjacent system components etc.). The device must not be operated above the
maximum permitted ambient temperature.
•
Do not put insulation around the signal converter. Make sure that the airflow around the
signal converter is sufficient. It is permitted to have insulation on the pipe or stilling well and
the process connection.
2.3.2 OPTIFLEX 3200 C (compact converter version)
Maximum limits for EPL Ga/Gb, EPL Gb, EPL Da/Db and EPL Db
WARNING!
An explosive atmosphere is a mixture of air and flammable gases, vapour, mist or dust in
atmospheric conditions. If you do not use the device in these conditions (T
atm
= -20...+60
°
C /
-4...+140
°
F and p
atm
= 0.8...1.1 barg / 11.60...15.95 psig), do an analysis of the risk of ignition.
T
atm
= atmospheric temperature and p
atm
= atmospheric pressure.
WARNING!
Make sure that the maximum process connection temperature and maximum ambient
temperature are not more than the values given in the tables.
Temperature
class
Maximum surface
temperature
Max.
process
temperature
or process
connection
temperature
Maximum ambient temperature
Aluminium housing
Stainless steel housing
4-20mA /
HART with
or without
optional
output
Fieldbus
(PA/FF)
Modbus RTU
4-20mA /
HART with
or without
optional
output
Fieldbus
(PA/FF)
Modbus RTU
[
°
C]
T6
T85
+60
+54
+50
+54
+50
+85
+51
+46
+51
+44
T5
T100
+75
+69
+65
+69
+65
+100
+66
+61
+66
+59
T4
T135
+110
+77
+72
+135
+69
+60
T3
T150
+150
+64
+52