4
ELECTRICAL CONNECTIONS
66
IFC 300
www.krohne.com
06/2009 - 4000069802 - MA IFC 300 R03 en
Pulse/frequency output passive, basic I/Os
•
U
ext
≤
32 VDC
•
f
max
in operating menu set to f
max
≤
100 Hz:
I
≤
100 mA
open:
I
≤
0.05 mA at U
ext
= 32 VDC
closed:
U
0, max
= 0.2 V at I
≤
10 mA
U
0, max
= 2 V at I
≤
100 mA
•
f
max
in the operating menu set to 100 Hz < f
max
≤
10 kHz:
I
≤
20 mA
open:
I
≤
0.05 mA at U
ext
= 32 VDC
closed:
U
0, max
= 1.5 V at I
≤
1 mA
U
0, max
= 2.5 V at I
≤
10 mA
U
0, max
= 5.0 V at I
≤
20 mA
•
If the following maximum load resistance R
L, max
is exceeded, the load resistance R
L
must be
reduced accordingly by parallel connection of R:
f
≤
100 Hz: R
L, max
= 47 k
Ω
f
≤
1 kHz: R
L, max
= 10 k
Ω
f
≤
10 kHz: R
L, max
= 1 k
Ω
•
The minimum load resistance R
L, min
is calculated as follows:
R
L, min
= (U
ext
- U
0
) / I
max
•
Can also be set as a status output; for the electrical connection, see status output connection
diagram.
INFORMATION!
•
For frequencies above 100 Hz, shielded cables are to be used in order to reduce radiation
from electrical interferences (EMC).
•
Compact and field housing versions:
Compact and field housing versions:
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
compartment.
Wall-mounted version:
Wall-mounted version:
Wall-mounted version:
Wall-mounted version: Shield connected using 6.3 mm / 0.25" push-on connectors
(insulation to DIN 46245) in the terminal compartment.
•
Any connection polarity.
Figure 4-27: Pulse frequency output passive P
p