C5.2 display
C5.2
display
C5.2.1
language
Language selection depends on the device version.
C5.2.2
contrast
Adjust display contrast for extreme temperatures.
Setting: -9
…
0
…
+9
This change takes place immediately, not just when setting mode is exited!
C5.2.3
default display
Specification of the default display page that is returned to after a short
delay period.
Select: none (the current page is always active) / 1. meas. page (show this
page) / 2. meas. page (show this page) / status page (show only status
messages) / graphic page (trend display of the 1st measurement)
C5.2.4
self test
Not available at this time.
C5.2.5
SW.REV.MS
Serial no. of the circuit board, version no. of user software, production date
of the circuit board
C5.3 and C5.4 1. meas. page and 2. meas. page
C5.3
1. meas. page
stands for 3 = meas. page 1 and 4 = meas. page 2
C5.4
2. meas. page
C5.
.1
function
Specify number of measured value lines (font size)
Select: one line / two lines / three lines
C5.
.2
measurement 1.line
Specify measurement for 1st line.
Select: volume flow / mass flow / diagnosis value / flow speed / coil
temperature / conductivity
C5.
.3
range
0
…
100% of the measurement set in Fct. C5.
.2
0
…
xx.xx _ _ _ (format and unit depend on the measurement)
C5.
.4
limitation
Limitation before applying the time constant.
xxx%; range: -120
…
+120%
C5.
.5
low flow cutoff
Sets output to "0": x.xxx
±
x.xxx %; range: 0.0
…
20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value
≤
1st value
C5.
.6
time constant
Range: 0.1
…
100 s
C5.
.7
format 1.line
Specify decimal places.
Select: automatic (adaptation carried out automatically) /
X (= none)
…
X.XXXXXXXX (max. 8 digits)
C5.
.8
measurement 2.line
Specify measurement 2.line (only available if this 2.line is activated)
Select: bar graph (for the measurement selected in 1.line) / volume flow /
mass flow / diagnosis value / flow speed / counter 1 / counter 2 / counter 3 /
conductivity / coil temperature
C5.
.9
format 2.line
Specify decimal places.
Select: automatic (adaptation carried out automatically) /
X (= none)
…
X.XXXXXXXX (max. 8 digits)
C5.
.10
measurement 3.line
Specify measurement 3.line (only available if this 3.line is activated)
Select: volume flow / mass flow / diagnosis value / flow speed / coil
temperature / conductivity / counter 1 / counter 2 / counter 3 / current
input A / current input B
C5.
.11
format 3.line
Specify decimal places.
Select: automatic (adaptation carried out automatically) /
X (= none)
…
X.XXXXXXXX (max. 8 digits)