TECHNICAL DATA
8
131
IFC 300
www.krohne.com
06/2009 - 4000069802 - MA IFC 300 R03 en
PROFIBUS DP
PROFIBUS DP
PROFIBUS DP
PROFIBUS DP
Description
Galvanically isolated acc. to IEC 61158
Profile version: 3.01
Automatic data transmission rate recognition (max. 12 MBaud)
Bus address adjustable via local display at the measuring device
Function blocks
5 x analogue input, 3 x totalizer
Output data
Volume flow, mass flow, volume counter 1 + 2, mass counter, velocity, coil
temperature, conductivity
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
Description
Galvanically isolated acc. to IEC 61158
Profile version: 3.01
Current consumption: 10.5 mA
Permissible bus voltage: 9
…
32 V; in Ex application: 9...24 V
Bus interface with integrated reverse polarity protection
Typical error current FDE (Fault Disconnection Electronic): 4.3 mA
Bus address adjustable via local display at the measuring device
Function blocks
5 x analogue input, 3 x totalizer
Output data
Volume flow, mass flow, volume counter 1 + 2, mass counter, velocity, coil
temperature, conductivity
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION Fieldbus
Description
Galvanically isolated acc. to IEC 61158
Current consumption: 10.5 mA
Permissible bus voltage: 9
…
32 V; in Ex application: 9...24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 5.1
Function blocks
3 x analogue input, 2 x integrator
Output data
Volume flow, mass flow, velocity, coil temperature, conductivity, electronics
temperature
Modbus
Modbus
Modbus
Modbus
Description
Modbus RTU, Master / Slave, RS485
Address range
1
…
247
Supported function codes
03, 04, 16
Broadcast
Supported with function code 16
Supported Baudrate
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud
.book Page 131 Wednesday, June 10, 2009 4:20 PM