Installation and operating instructions
IFC 020
4/12
Examples of setting the signal converter 4.7
As an example the
cursor,
flashing part of display, is shown below in
bold
type.
•
Change measuring range of current output and value for error messages
(Fct. 1.05):
•
Change measuring range from 04-20 mA to
00-20 mA
•
Change value for error messages from 0 mA to
22 mA
Key
Display
Description
→
If “YES” set under Fct. 3.04 ENTRY CODE, key in the
9-keystroke CODE 1 now:
→ → → ↵ ↵ ↵ ↑ ↑ ↑
Fct. 1.00
OPERATION
→
Fct. 1.
01
FULL SCALE
4x
↑
Fct. 1.
05
CURRENT I
→
FUNCT. I
→ ↵
RANGE I
→
04-20
mA
Old current range
↑
00-20
mA
New current range
↵
I ERROR
→
0
mA
Old value for error messages
2x
↑
22
mA
New value for error messages
↵
Fct. 1.
05
CURRENT I
↵
Fct. 1.00
OPERATION
↵
STORE YES
↵
- - - - - - -
- - - - - / - - -
Measuring range with new data for the current output