TECHNICAL DATA
8
85
H250 M40
www.krohne.com
03/2020 - 4000640706 - MA H250-M40 R06 en
ESK4-T with LCD, binary inputs and outputs and digital counter
Binary output
Two binary outputs
Galvanically isolated, passive
Mode
Switching output
NAMUR or transistor (OC)
Configurable as
switch contact or pulse output
NC / NO or max. 10 pulses/s
NAMUR switching output
Power supply
8.2 VDC
Signal current
> 3 mA switching value not reached;
< 1 mA switching value reached
Switching output transistor (Open Collector)
Power supply
Nominal 24 VDC, maximum 30 VDC
P
max
500 mW
Continuous current
Max. 100 mA
No load current I
0
≤
2 mA
Pulse output
T
on
Configurable from 50...500 ms
T
off
Depending on flow rate
Pulse weight
Configurable in flow units e.g. 5 pulses/m
3
Binary input
Input
Galvanically isolated
Mode
Reset counters or Start / Stop
Configurable as
active HI / active LO
H signal
16...30 VDC
Internal resistance R
i
Typical 20 k
Ω
T
on
(active)
≥
500 ms
LC display
Technology
Passive graphic LCD
Display
Measurement with units and/or counter reading with units.
Counter reading max. 11-digit with power failure proof storage.
Binary flags for limit value status. 0...100% bargraph for measurement.
NE 107 diagnostic status symbols. Plain text menu for configuration.
Configuration
Local plain text menu navigation via microswitch or bar magnet or using
DD/DTM software
Table 8-13: ESK4-T with LCD, binary inputs and outputs and digital counter