Follow vent pipe manufacturer‟s installation instructions for horizontal terminations. Include required 3” (76 mm) top cleara
nce (at wall pass-thru)
and 1” (25 mm) sides and bottom clearances for approved rigid vent systems.
CAUTION: Due to high temperatures, this fireplace should be located out of traffic areas and away from furniture and draperies.
HORIZONTAL TERMINATIONS
Follow vent pipe manufacturer‟s installation instructions for vertical terminations. A minimum 1” (25 mm) clearance on all s
ides of vertical vent
pipe must be maintained.
VERTICAL TERMINATIONS
FRAMING
IMPORTANT: Vent cap location must be in compliance with guidelines on page 19
of this manual
.
IMPORTANT: KOZY HEAT WALL THIMBLE PASS-THRU (#800-WPT or #800-WPT2) MUST BE USED ON ALL HORIZONTAL
VENT RUNS. FOLLOW INSTRUCTIONS ON PAGE 15 OF THIS INSTALLATION MANUAL.
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD INCLUDED WITH THIS FIREPLACE MUST BE INSTALLED WHEN
USING A 90-DEGREE ELBOW DIRECTLY OFF TOP OF UNIT TO HORIZONTALLY POSITION VENT SYSTEM.
PAGE 9
CAUTION: Cold air transfer area. The surrounding fireplace chase must comply with all clearances as outlined in this manual and be constructed
in compliance with local building codes. Outside walls should be insulated to prevent cold air from entering room.
32-
5/8”
(829 mm)
19-
3/4”
(502 mm)
MINIMUM HORIZONTAL FRAMING DIMENSIONS
VENT PIPE TOP (A)
FRAMED OPENING TOP (B)
TERMINATION WIDTH (W)
TERMINATION HEIGHT (H)
RIGID PIPE
41-
1/4” (1048 mm)
44-
1/4” (1124 mm)
10-
7/8” (276 mm)
12-
1/2” (318 mm)
IMPORTANT: Header must be positioned „up‟ to maintain proper
clearances from vent system to combustibles.