background image

DIRECT VENT 

GAS FIREPLACE HEATER

MODEL SERIES

DVP36PP32EN-1

DVP36PP32EP-1

DVP36SP32EN-1

DVP36SP32EP-1

UL FILE NO. MH30033

INSTALLATION INSTRUCTIONS

AND

OWNER’S MANUAL 

WARNING: If not installed, operated and maintained 

in accordance with the manufacturer’s instructions, 

this product could expose you to substances in fuel or 

from fuel combustion which can cause death or seri-

ous illness.

This  appliance  may  be  installed  in  an  aftermarket, 

permanently located, manufactured home (USA only) 

or mobile home, where not prohibited by state or local 

codes.
This  appliance  is  only  for  use  with  the  type  of  gas 

indicated  on  the  rating  plate.  This  appliance  is  not 

convertible for use with other gases, unless a certified 

kit is used.

The Tahoe Direct Vent Zero Clearance Gas 

Fireplace Heater

GAS-FIRED

Installer:  Leave this manual with the appliance.

Consumer:  Retain this manual for future reference.

—  Do not store or use gasoline or other flammable 

vapors  and  liquids  in  the  vicinity  of  this  or  any 

other appliance.

—  WHAT TO DO IF YOU SMELL GAS

 

•  Do not try to light any appliance.

 

•  Do not touch any electrical switch; do not use 

any phone in your building.

 

•  Immediately  call  your  gas  supplier  from  a 

neighbor’s  phone.  Follow  the  gas  supplier’s 

instructions.

 

•  If you cannot reach your gas supplier, call the 

fire department.

—  Installation and service must be performed by a 

qualified installer, service agency or the gas sup-

plier.

WARNING: If the information in these instructions 

are not followed exactly, a fire or explosion may re-

sult causing property damage, personal injury or 

loss of life.

Page 1

Summary of Contents for Tahoe DVP36PP32EN-1

Page 1: ...gases unless a certified kit is used The Tahoe Direct Vent Zero Clearance Gas Fireplace Heater GAS FIRED Installer Leave this manual with the appliance Consumer Retain this manual for future reference Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric...

Page 2: ...1 Examples Rear Vent Run 32 Termination Clearances 33 Vent Clearances 34 Vent System Identification 35 Framing and Finishing 36 37 Horizontal Termination 38 DVVK 4RE Vent Kit Installation Instructions 39 41 DVVK 4F Flex Vent Instructions 42 Vertical Termination 43 44 Placement of Glowing Embers 45 Operation Instructions Flame Appearance 46 Operating Instructions 47 48 Standing Pilot Wiring Diagram ...

Page 3: ...RDWARE PACKAGE Note Hardware shown to scale where possible 10 X PHILLIPS HEX HEAD SCREW 24 PENINSULA MODELS 16 SEE THROUGH MODELS NAILING FLANGE 8 CORNER TIE CANOPY 2 PENINSULA MODELS ROMEX CONNECTOR 2 8 18 x PHILLIPS TRUSS HEAD SCREW 4 PENINSULA MODELS Additional Parts for Peninsula Models Only Canopy End Canopy Right Canopy Left End Shield Canopy Corner Tie Note Installation required when using ...

Page 4: ...s front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment clean Vent cap is hot while fireplace is in operation Installation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a qualified servi...

Page 5: ...s perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstalled ...

Page 6: ...isions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...

Page 7: ...of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from the American National Standards Institute Inc 11 West 42nd St New York N Y 10036 Any alteration of the original design installed other than as shownintheseinstructionsorusewithatypeofgasnotshownon the rating plate is the responsibility of the person an...

Page 8: ...zontal Round Termination wall thickness 5 to 13 3 4 DV822 Vinyl Siding Kit for DVVK 4RE DVVK 4FV Vertical Flex Vent Kit 6 Flex 4 Rigid 10 Total DVEK 10 10 Vent Extension Kit DVEK 25 25 Vent Extension Kit NOTE Air shutter settings are factory minimum settings Some venting configurations may require minor air shutter adjustments for optimum performance SPECIFICATIONS DVP36 SP PP Nat Models Input Btu ...

Page 9: ... D D M M N N A A H H J I I 17 21 HORIZONTAL VENT CONNECTION SEE THRU PENINSULA J G MODEL DVP36SP32E DVP36PP32E A 34 3 4 34 3 4 B 39 39 C 24 24 D 22 22 E 36 36 F 29 1 4 32 5 8 G 22 22 H 41 1 8 41 1 8 I 1 1 4 1 1 4 J 5 3 8 5 3 8 K 2 1 2 2 1 2 L 6 6 M 25 25 N 33 1 2 33 1 2 MAX WEIGHT LB 240 230 ...

Page 10: ...D MANTELS ALLOWED IN SHADED AREA Clearance to Combustibles Air Drop End 1 2 12 7 mm Side 1 2 12 7 mm Floor 0 0 mm Top Stand off 0 0 mm Top Framing Edge 6 3 8 161 7 mm GLASS FRONT 6 3 8 SEE MANTLE CHART FOR MAXIMUM MANTLE DEPTH 2 x 4 HEADER STAND OFF 3 76 mm HEIGHT ABOVE TOP OF FIREPLACE NAILING FLANGES TOP FRAMING LEDGE NON COMBUSTIBLE FIRST 6 3 8 SEE MAGNIFIED VIEW FINISHED WALL COMBUSTIBLE SEE M...

Page 11: ... with the mitered corner to the open end of the fireplace The canopy will slide under the flange of the Rear Mantel Corner Bracket Align the holes in the canopy with the cor ner bracket and loosely install a 10 x 1 2 Hex Head screw to re tain 3 Position the Front Canopy with the mitered corner to the open end of the fireplace The canopy will slide under the Rear Mantel Cor ner Bracket Align the holes...

Page 12: ... install your Direct Vent Fireplace a minimum of 1 3 4 inches clearance must be maintained from the perpendicular wall and the front opening of the appliance However on the vent end of the fireplace if placed against a wall the perpendicular side wall clearance from the opening would be 2 1 2 inches C ISLAND INSTALLATION SEE THRU H D ROOM DIVIDER INSTALLATION PENINSULA D ROOM DIVIDER INSTALLATION S...

Page 13: ...g 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have a built in pressure regulator in the gas valve Natural gas models will have a manifold pressure of approximately 3 5 w c 871kPa at the valve outlet with the inlet pressure to the valve from a minimum of 4 5 w c 1 120kPa for the purpose of input adj...

Page 14: ...inlet vent collar to the rear of the fireplace with 8 screws 7 This completes the conversion for a rear vent application SPECIAL VENT SYSTEMS The following vent systems are acceptable for use with the DVP36 SP PP series fireplaces Simpson Duravent PRO Series 4 6 Selkirk Direct Temp 4 6 Metal Fab Sureseal 4 6 1 2 Note Adapter pipe starter required Empire Horizontal Round Termination Kit DVVK 4RE refe...

Page 15: ...he installation for the fireplace it is necessary to determine where the unit is to be installed and whether optional accessories are desired Gas supply piping should also be planned at this time A gas shutoff must be installed in this line The fireplace can be mounted on any of these surfaces 1 A flat hard combustible or non combustible surface 2 A raised platform of combustible or non combustible m...

Page 16: ...ial Use at least one 1 nail or screw per bracket to secure in place IMPORTANT Check squareness of all openings of the fireplace prior to securing to the framed openings See Figure 14 NOTE On See Through models framing brackets may be placed on one side of the facing openings This allows the fireplace to be inserted into the pre framed opening Figure 13 CHECK TO SEE THAT BOX IS SQUARE PRIOR TO ATTACH...

Page 17: ...y non combustible material using 300 F minimum adhesive if needed can be applied as facing to the fireplace surround Flush Wall Installation See Through Models Figure 16 Flush Mount Mantel Installation See through Models Only Figure 15 The fireplace must extend 3 4 beyond finished wall surface when using a flush mount mantel on see through models Refer to Figure 15 to locate nailing flanges on fireplace...

Page 18: ...o applicable insulation codes Vent Runs In planning the installation for the fireplace it is necessary to install certain components before the appliance is completely positioned andinstalled Theseincludethedirectventsystem gaspipingforthe appliance and the electrical wiring If the fan option is used In addition to non combustible surfaces the appliance can be mounted on any of the following surfac...

Page 19: ...VENT CAP NOTE 1 FOOT VERTICAL VENT MIN REQUIRED WHEN TOP VENTING WITH HORIZONTAL TERMINATION 9 229 MM MINIMUM WALL FIRESTOP THIMBLE C B A B C 6 11 1 4 to 12 3 4 4 3 4 to 6 1 4 9 14 1 4 to 15 3 4 7 3 4 to 9 1 4 12 17 1 4 to 18 3 4 10 3 4 to 12 1 4 INSTALLATION continued HORIZONTAL ONLY STRAIGHT OUT THE BACK Figure 20 VERTICAL 90 ELBOW TO HORIZONTAL OUT THE WALL ...

Page 20: ...is does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3 for every 90 elbow Example According to the chart the maximum horizontal vent length is 20 and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17 The maximum number of 45 degree elbows permitted per side wall installation is two 2 These elbows can be installed ...

Page 21: ...h the wall Ensure the sidewall venting clearances are observed If venting system is installed below ground we recommend a window well with adequate and proper drainage to be installed around the termination area TYPICAL BASEMENT INSTALLATION Figure 23 Examples of possible venting systems using one 1 90 elbow Eight 8 feet is listed as minimum vertical vent run with 20 feet of maximum horizontal ven...

Page 22: ...orizontal run of the termination See Figure 26 When locating the hole it must be noted that the bottom of the cap must be 12 305mm above the ground level and top of the cap must be no less than 18 457mm below a combustible projection and no closer than 9 229mm to any wall running parallel to vent termination See Figure 27 SEE VENT CHART FOR PERMISSIBLE H AND V DIMENSIONS 1 FOOT VERTICAL PIPE REQUI...

Page 23: ...alified field service person Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow In spect entire venting system to ensure proper function Please refer to the fireplace instructions for information on Termination Cap clearances This vent kit may be installed as an OEM installation in a manufactured home USA only or mobile home and must be install...

Page 24: ...e Vertical Flex Termination Kit WARNING Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches 305mm above the roof WARNING Refer to your fireplace homeowner s manual for the minimum and maximum venting requirement of your fireplace prior to installa tion Failure to do so may cause a fire hazard WARNING This flexible pipe termination kit is ONLY ...

Page 25: ... enough to provide a mini mum 1 air space clearance from the vertical vent pipe to any combustible framing 6 Install the Firestop Thimble assembly to the framed opening in the ceiling using common nails or screws Note The thimble assembly is adjustable up or down as needed within the firestop It is also designed with a pivoting firestop for use with 0 3 12 pitch cathedral ceilings 7 To begin vent sy...

Page 26: ... cutout opening see step 5 Feed the flex vent end down through the roof opening and firestop thimble assembly installed in steps 4 through 6 14 Secure the roof support assembly to the roof sheathing with at least 4 nails screws through each support bracket Check that the combustible clearances through the roof framing will maintain at least a 1 clearance from the vent pipe 15 Determine how high the ...

Page 27: ...d as an attic insulation shield The collar can be installed around the flex pipe or hard pipe just above the firestop thimble This collar will act as a shield to prevent blown in sulation from entering the thimble 22 To complete the vent installation install the vent termination cap to the top of the hard vent pipe assembly Mate up the flue and outer telescopes with the hard pipe assembly then secure...

Page 28: ...OP THIMBLE 4 DIA FLUE CONNECTOR 7 DIA ADAPTER COLLAR WITH GASKET CLAMPS SEE THRU DIRECT VENT FIREPLACE NOTE DVVK 4FV KIT MAXIMUM HEIGHT INCLUDING FIREPLACE IS 13 TO EXTEND VENT RUN AN ADDITIONAL VENT EXTENSION KIT IS NECESSARY VENTING SUPPORT STRAPS AS REQ D 35 MAX CEILING ADJUSTABLE FIRESTOP THIMBLE ASSEMBLY CLEARANCE TO COMBUSTIBLES REQUIRED FROM VENT PIPE ADJUSTABLE ROOF JACK ASSEMBLY STORM COL...

Page 29: ...ter by 6 ft MF07ALA2F006 1 5 4 7 x 48 Rigid Pipe Assembly MF100554 1 6 Firestop Thimble Assembly MF100124 1 7 Roof Flashing 0 12 to 6 12 MF100091 1 8 7 Flex Adapter Collar with Gasket MF100524 1 9 7 Storm Collar MF100147 2 10 Spring Spacers MF100548 5 N S Clamp 4 Diameter MF100330 2 N S Clamp 7 Diameter MF100534 2 N S 8 x 1 2 Self Drilling Screws N A 20 N S HT Silicone N A 1 N S 8 x 5 8 Self Drill...

Page 30: ...36 Figure 37 Figure 38 24 MINIMUM CLEARANCE TO COMBUSTIBLES 24 Example H2 2ft 2 90 90 6ft V1 21ft H 8ft V 15ft Example H2 3ft H3 1ft 4ft 90 90 90 6ft V1 21ft H 10ft V 21ft Example H1 2ft V1 20ft H 2ft V 20ft EXAMPLES TOP VENT RUN ...

Page 31: ...d dimension and position the unit in accordance with same EXAMPLE A If the vertical dimension from the floor of the unit is 12 feet 4 inches the horizontal run to the outer wall flange must not exceed 12 feet 3 inches EXAMPLE B If the vertical dimension from the floor of the unit is 6 feet 9 inches the horizontal run to the outer wall flange must not exceed 6 feet 6 inches SPECIAL NOTE For each 45 deg...

Page 32: ...24325 0 0708 Page 32 Figure 40 Figure 41 Figure 42 Figure 43 H1 18 MAX H1 18 inches max Model Maximum Pipe Length H1 DVP36 SP PP 18 Model Maximum Pipe Length H1 DVP36 SP PP 18 EXAMPLES REAR VENT RUN ...

Page 33: ...place in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust certain limitations as to vent configurations apply and must be strictly adhered to The graph showing the relationship between vertical and horizontal side wall venting will help to deter...

Page 34: ...er line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 inches 30cm minimum for appliances 100 000 Btuh 30 kW 36 inches 90cm minimum for appliances 100 000 Btuh 30kW K clearance to a mechanical air supply inlet 6 feet 1 8m minimum L clearanceabovepaveds...

Page 35: ...ERTICAL TERMINATION MAXIMUM OF THREE 90 ELBOWS STORM COLLAR ROOF FLASHING WALL THIMBLE HORIZONTAL TWO 90 ELBOWS TERMINATION MAXIMUM OF 90 ELBOW OR 45 ELBOW 90 ELBOW CEILING FIRESTOP WALL STRAP PIPE LENGTH Special venting components Simpson Duravent See Empire Comfort Systems Retail Price List for Simpson Duravent part numbers and pricing Special DV Vent Kits Available from Empire Comfort Systems I...

Page 36: ...e previously cut Secure with nails or screws The heat shields of the firestops MUST BE placed towards the top of the hole Continue the vent run through the firestops See Figure 48 10 11 Figure 48 Vertical runs of this system which pass through ceilings require the use of ONE 1 ceiling firestop at the hole in each ceiling through which the vent passes Position a plumb bob directly over the center of t...

Page 37: ...24325 0 0708 Page 37 Figure 51 FRAMING AND FINISHING continued Figure 49 Figure 50 ...

Page 38: ... to install a vinyl siding standoff The vinyl siding standoff will be installed between the vent terminationandtheexteriorwall SeeFigure52 Thishorizontalvent terminationboltsontotheflatportionofthevinylsidingstandoff so an air space will exist between the wall and the termination cap Figure 52 For installations requiring a vertical rise on the exterior of the building 14 inch and 36 inch tall Snork...

Page 39: ...er or not the extension thimble is to be used If the combustible wall depth is over 5 3 8 137mm then the extension thimble should be used Figure 54 3 Install the wall thimble assembly through the framed opening so the firestop plate is on the interior wall Figure 54 Telescope section should extend all the way through the exterior wall Attach with 4 10 x 1 screws 4 When placing the vent cap on an ex...

Page 40: ...gid venting system using 3 self tapping screws 12 Seal the 4 102mm diameter flue outlet tube Follow instructions and diagram Figure 58 13 Fasten4 102mm diameterflueoutlettubeinplace Donot twist the flue outlet tube into the fireplace collar or rigid venting sys tem Hold the tube by the seam and push in using a perpendicular rocking motion This ensures the seam on the tube stay intact 14 Fasten vent ca...

Page 41: ... high temperature sealant to the opposite end of the tube on the inside of the tube The end with the gasket will attach to the back of the unit Continue with Step 13 Connecting to Rigid Vent System If the air inlet and flue outlet tubes are to be connected to a rigid venting system and not directly to the back of the unit then do not use the gasket provided High temperature sealant should be applie...

Page 42: ... Secure flue adapter to the fireplace flue with a minimum of two screws provided See Figure C 11 Attach the Outer Vent pipe to the 7 diameter Collar on the fireplace with a large band clamp provided Sealant may also be used on the outer vent connections 12 Check all vent connections for tightness Make sure horizontal venting has the proper rise and combustible clearances required Refer to venting ...

Page 43: ...streaks and in extreme cases holes These components should immediately be replaced 2 Remove the cap and shine a flashlight down the vent Remove any bird nests or other foreign material 3 Check for evidence of excessive condensate such as water droplets forming in the inner liner and subsequently dripping out at joints Condensate can cause corrosion of caps pipe and fittings It may be caused by havin...

Page 44: ... high wind vertical top Please refer to the instructions included with the Air Inlet Baffle Kit for proper installation Reassembly and Resealing Vent Pipe System Attachventpipetoinletandoutletventadaptoronfireplaceineither the vertical or horizontal position replace horizontal and vertical pipe lengths elbows and horizontal or vertical termination kit All rigid pipe vent system components lock into ...

Page 45: ...e rockwool will break down and new rockwool will need to be placed to recreate the original glowing embers effect Remove all old rockwool from the appliance and apply new rockwool as shown in Figure 63 Note Only the rockwool supplied with this unit or ordered in accordance with the Parts List on page 53 should be used on this burner See the Parts List on page 53 to order replacement rockwool Optio...

Page 46: ...noying smoke and smells as they are burned off during the initial operation of the appliance possibly causing headaches or eye or lung irritation This is a normal and temporary occurrence The initial break in operation should be 5 to 10 minutes on at the highest setting then let cool for 10 to 15 minutes Repeat this On Off cycle two to three times to cure sealants Provide additional ventilation by...

Page 47: ...time period allows the millivolts electrical current to build up to a sufficient level allowing the gas control to operate properly 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for standing pilot controls found in this manual and on labels found in control compartment behind the door assembly CAUTION Duringtheinitialpurgingandsubsequentlightings never allow the gas valve control knob to remain dep...

Page 48: ...er that is a component in the FREC Turn the REMOTE OFF ON switch to the REMOTE position Follow instructions in the FREC to complete installation NOTE If electric 120 colt fails in FREC and immediate heat is desired turn the REMOTE OFF ON switch from the REMOTE position to the ON position Reassembly and Resealing Gas Accumulation Relief System Glass Frame Assembly and Combustion Chamber Whenever th...

Page 49: ...24325 0 0708 Page 49 Figure 66 OPTIONAL THERMOSTAT OPTIONAL WALL SWITCH STANDING PILOT WIRING DIAGRAM ...

Page 50: ...EPLACE FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B Before lighting smell all around the appliance area for gas Be sure to smell next to the floor b...

Page 51: ...the pilot flame Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading atTH TP TPterminals of the gas valve The meter shouldread350millivoltsminimum whileholdingthevalve knob depressed in the PILOT position with the pilot lit and the REMOTE OFF ON s...

Page 52: ...particles to cling to the glass surface Also initial paint curing may deposit a slight film on the glass It is therefore recommended that the glass be cleaned two or three times with a non abrasive household cleaner and warm water we recommend gas fireplace glass cleaner After that the glass should be cleaned two or three times during each heating season depending on the circumstances present Genera...

Page 53: ... 19401 19401 BRICK LINER BRACKET 23 24710 24710 BURNER ASSEMBLY 24 24144 24144 GRATE ASSEMBLY 25 24282 24282 BURNER SUPPORT 26 24283 24283 BURNER BASE 27 11269 11269 GAS LINE BRACKET 28 24296 24296 TUBING ASSEMBLY 29 R2423 R2423 MALE 5 16 X 3 8 NPT CONNECTOR 30 R7577 R7577 VALVE NAT 30 R7578 R7578 VALVE LP 31 17161 17161 VALVE BRACKET 32 R3436 R3436 REMOTE OFF ON SWITCH 33 R9760 R9760 PIEZO IGNITO...

Page 54: ...24325 0 0708 Page 54 DVP36SP PARTS VIEW 1 2 2 5 6 7 8 9 10 11 12 13 14 15 16 18 18 19 20 21 22 22 23 24 24 25 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 40 41 42 43 44 3 3 4 4 17 17 5 5 5 5 5 5 ...

Page 55: ...0 0708 Page 55 DVP36PP PARTS VIEW 1 2 2 5 5 5 5 6 7 8 9 10 11 12 13 14 15 16 17 17 18 19 20 21 22 22 23 24 25 25 26 27 28 29 30 47 48 49 50 51 52 31 32 33 34 35 36 37 38 39 40 40 41 42 43 44 45 46 3 3 4 4 24 ...

Page 56: ...e remove the tab on the side of the receptacle hot side to split receptacle This will be required to separate blower and Accent Light circuits 2 Power for switched and live sides of Duplex Receptacle must come from the same power source One circuit breaker on main panel must switch all power off 3 From the wall box to the fireplace a 3 wire conductor with ground is recommended however 2 two wire co...

Page 57: ...e This frame retains the glass lens The bulb can now be accessed Note Do not handle the lamp bulb with bare fingers protect with clean dry cloth The lamp will pull straight out of the socket Replace with 10 Watt 12 Volt Halogen bulb When re installing ensure integrity of gasket seal THE FIREBOX MUST BE SEALED Over tightening the screws could break the lens Light Leakage from the upper area may be o...

Page 58: ...nstallation of the wiring be performed by a qualified electrician See Figure 70 1 If installed turn OFF gas supply to fireplace 2 If applicable turn OFF electric supply to fireplace 3 Remove bottom louver from fireplace CAUTION ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL CITY AND STATE BUILDING CODES BEFORE MAKING THE ELECTRI CAL CONNECTION MAKE SURE ...

Page 59: ...by letters A and B in Figure 75 on page 60 7 Route the wires away from moving parts of the blower as sembly and retain wires together near the blower motor using the plastic purse clip provided 8 To complete the installation plug the power cord into the junction box receptacle previously installed in the bottom of the fireplace See Figures 70 and 71 9 Once all connections are made electrically it i...

Page 60: ...ug can be plugged into the adapter and be electrically grounded CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Blower Motor The blower motor does not have oiling holes Do not attempt to oil the blower motor Blower Wheels The blower wheels will collect lint and could require peri...

Page 61: ...Decorative Frame Rectangle with hinges Decorative Door Leaf Rectangle Decorative Door Mission Rectangle Decorative Door Plain Rectangle Decorative Frame Arch with hinges Decorative Door Leaf Arch Decorative Door Mission Arch Decorative Door Plain Arch Outside Frame Kits See through models only STD Louvers 45 Deg Window Trim Decorative Frame Arch without hinges only Black ACCESSORIES Accessory Desc...

Page 62: ...nt Then determine the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fireplace Serial Number Part Number Type of Gas Propane or Natural Do not order bolts screws washers or nuts They are standard hardware items and can be purchased at any local hardware sto...

Page 63: ...24325 0 0708 Page 63 SERVICE NOTES ...

Page 64: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer www empirecomfort com ...