PAGE 28
NCL-195 INFORMATION
ELECTRICAL WARNING AND INFORMATION:
Electrical wiring must be installed by a licensed electrician.
Do NOT wire 110V to wall switch.
Uninterrupted or continuous power is required at all times in IPI systems EXCEPT when using battery back-up.
Incorrect wiring will override IPI safety lockout and may cause an explosion.
Disconnect 110V before servicing
A double receptacle box cover and (3) wire nuts are supplied in fireplace components packet to be used when hardwiring to electrical box
located under firebox on right side of fireplace.
The IPI gas control system has the option of a continuous (standing) pilot feature. This allows the user to change from a spark to pilot system to
a standing pilot system for direct vent appliances during cold weather conditions. By having the pilot on continuously, the firebox will remain
warm and a draft is established in the vent, allowing main burner to turn on with less air-flow disruption.
When continuous pilot mode is activated and fireplace is turned ON, the pilot will spark and light. When fireplace is turned OFF, the pilot will
remain lit when main burner has been turned OFF.
This pilot feature can be activated or de-activated by the hand held remote control transmitter. Please follow instructions on page 28.
CONTINUOUS PILOT (
FOR VERY COLD CONDITIONS)
OPERATION USING BATTERY POWER
This fireplace has an optional battery operation if electrical power is lost. Position battery pack with four “AA” size batt
eries installed
between valve and front of fireplace. This is the coolest location under firebox, ensuring longer battery life.
Before matching security codes make sure 120V AC is connected and powered
to fireplace, and hand held remote control is installed with (2) AA batteries.
It may be necessary to program main control module to LEARN the security
code of the hand held remote control upon initial use, if batteries are replaced, or
if a replacement remote control is purchased from your dealer.
1. When matching security codes, be sure slide button on main control module
is in
REMOTE
; the code will not “LEARN” if slide is in
OFF
.
2. Program main control module to LEARN a new security code by pushing in
LEARN
button on main control module using a pencil point (you should
hear a single „beep‟ letting you know module is ready to learn a new code).
3.
Press any button on hand held remote control (you should hear four „beeps‟
in rapid succession in main control module, indicating remote control‟s code
has been programmed into the main control module). When an existing
main control module is introduced to a new hand held remote control, the
new security code will overwrite the old one.
If it ever becomes necessary to clear the memory from the hand held remote
control, simply push and hold the
LEARN
button for 10 seconds (you should
hear three long beeps in succession). You may now follow steps outlined above
to „RE
-
LEARN‟ security codes.
MATCHING SECURITY CODES
LEARN BUTTON
SLIDE TO REMOTE POSITION
ATTENTION: THIS SYSTEM GOES THROUGH A CALIBRATION MODE WHEN SWITCHING FROM ON TO THERMO TO OFF
MODES, CREATING A HUMMING SOUND WHICH IS A NORMAL PART OF OPERATION.
NOTE: When operating fireplace in this capacity, the only function available is flame modulation.