B
B
L
DENOTES WHERE INSTALLATION NOT ALLOWED
J
K
C
G
P
H
I
O
D
E
A
N
F
M
1. Terminations against vinyl siding must use a vinyl siding protector. Follow instructions included.
2. DO NOT RECESS TERMINATION KIT INTO OUTSIDE BUILDING MATERIALS - i.e.: brick, stone, siding, etc.
If necessary, extend framing so that termination kit will be exposed once building materials are installed.
3. Vent termination must not be located where it will become plugged by snow or other material. The flow of combustion
and ventilation air must be not obstructed.
A. Above grade, veranda, porch, deck, balcony - 12" (305 mm).
B. Operable window or door -
CANADA: 12" (305 mm). US: 9” (229 mm).
C. Permanently closed window* - 12" (305 mm) (recommended to prevent condensation on window).
D. Ventilated soffit* - 18" (457 mm).
E. Unventilated soffit* - 11" (279 mm).
F. Outside corner* - 1" (25 mm).
G. Inside corner* -
0” (0 mm).
H. Gas Service regulator vent outlet - 3 ft. (914 mm)
I.
Meter / Regulator: Not to be installed above a gas meter/regulator assembly within 3 ft. (914 mm) horizontally from
the centerline of the regulator.
J.
Non-mechanical air supply inlet to building or the combustion air inlet to any other appliance. CANADA: 12" (305 mm).
US: 9” (229 mm).
K. Mechanical air supply inlet. CANADA: 6 ft. (1.83 m) US: 3 ft. (914 mm) above if within 10 ft. (3.05 m) horizontally.
Massachusetts installations: 10 ft. (3.05 m).
L.
Above paved side-walk or paved driveway located on public property - 7 ft. (2.13 m).
This gas appliance must not be connected to a chimney serving any other appliance.
TERMINATION VENT CAP LOCATION
PAGE 19
LOCATION CLEARANCES
M. Under veranda, porch, deck, or balcony (must be fully opened on a min. of 2 sides) - 12" (305 mm).
N. Between two horizontal terminations - 12" (305 mm).
O. Between two vertical terminations - 12" (305 mm). Terminations may be the same height.
P. Above furnace exhaust or inlet - 12" (305 mm).
*Clearance must be in accordance with local installation codes & the requirements of the gas supplier.
NOTE: A vent cannot be located directly above a side-walk or paved driveway that is located between two single family dwellings and
serves both dwellings
.
Summary of Contents for Nicollet NCL-195
Page 43: ...PAGE 42...
Page 44: ...PAGE 43...