AKD-C Installation | 4 Handling
4.1 Packaging
The AKD-C packaging consists of recyclable cardboard with inserts and a label on the out-
side of the box.
Model
Package Dimensions
(mm) HxWxL
Total Weight
(kg)
AKD-C01007
125 x 410 x 295
5
4.2 Transport
Transport the AKD-C in accordance with IEC 61800-2 as follows:
Transport only by qualified personnel in the manufacturer’s original recyclable packaging.
Avoid shocks while transporting.
Store at or below maximum stacking height of 8 cartons
Transport only within specified temperature ranges: -25 to +70 °C, max. rate of change 20
K/hour, class 2K3.
Transport only within specified humidity: maximum 95% relative humidity, no con-
densation, class 2K3.
The devices contain electrostatically sensitive components that can be damaged by incor-
rect handling. Electrostatically discharge yourself before touching the device. Avoid contact
with highly insulating materials, such as artificial fabrics and plastic films. Place the device
on a conductive surface.
If the packaging is damaged, check the unit for visible damage. Inform the shipper and the
manufacturer of any damage to the package or product.
4.3 Storage
Store the AKD-C in accordance with IEC 61800-2 as follows:
Store only in the manufacturer’s original recyclable packaging.
Store at or below maximum stacking height of 8 cartons
Store only within specified temperature ranges: -25 to +55 °C, max.rate of change 20
K/hour, class 1K4.
Storage only within specified humidity: 5 to 95% relative humidity, no condensation, class
1K3.
Store in accordance with the following duration requirements:
Less than 1 year: without restriction.
More than 1 year: capacitors must be re-formed before setting up and operating the
drive. Re-forming procedures are described in the Kollmorgen Developer Network
(
).
4.4 Decommissioning
Only professional staff who are qualified in electrical engineering are allowed to decom-
mission parts of the system.
DANGER
: Lethal Voltages!
There is a danger of serious personal injury or death by electrical shock or electrical arcing.
Switch off the main switch of the switchgear cabinet.
Secure the system against restarting.
Block the main switch.
Wait at least 7 minutes after disconnecting.
18