-4-
(
)
!
!
NOTE:
For Retrofit Installations
For New Installations
If a pre-existing waste pipe will be used and will result
in an acceptable rim height (refer to the rough-in dimensions),
follow the retrofit installation instructions.
Turn the water supply line off, remove the existing urinal,
then cap off the water supply line inside the wall.
Install waste pipe as necessary to conform to the
roughing-in dimensions.
!
!
Fig.2
2
PREPARE THE SITE
PREPARE THE SITE
Draw lines
according to
the template.
110mm Drain pipe
110mm
Finished Wall
150
*
Draw centerline.
Draw lines according
to height of the
mounting hole center.
Connect the right
and left lines. Drill
holes on the center.
Electronic components are pre-installed in factory.
Electronic Components Installation
Electronic Components Installation
800
No object within 800mm of the
width of the sensor bilateral symmetry
800mm
No objects in the
Sensor before
1000mm
1000mm
Clapboard suggest
reference length is 450mm
450mm
450
1000
Notice:
To ensure an effective flush performance,
strongly recommended inner diameter of
water supply (including water meter, valve,
etc.) is no less than 25mm, and supplied
water pressure (sensor inlet dynamic
pressure) is 0.18MPa ~0.55MPa.
(
)
25mm
(
)
0.18MPa ~0.55MPa
1356730-T01-B