Installation
MF2933/BIR3
Bradley •
215-1371 Rev. M; ECN 12-00-013
11/27/2012
9
LOWER
BRACKET
FRONT
PANEL
SCREW
UPPER
BRACKET
7
Check Operation
A
Check to make sure both stops are fully
open (see page 6) .
B
Turn on the main water supply to the
Tri-Fount and check for leaks .
C
Turn on the electrical power and pass
your hand in front of each sensor until air
is purged from the lines .
This valve is NOT factory preset. Upon installation, the
temperature of this valve must be checked and adjusted
to ensure delivery of a safe water temperature. Water in
excess of 110°F (43°C) may cause scalding.
H
C
D
Loosen Cap Screw about ¼" (4-6 turns)
and lift up cover (do not remove) .
E
Using cover, turn cartridge gently until
desired water temperature is reached . Do
not turn past stops as this may damage
unit . Push cover down and tighten screw .
8
Install Top Cover and Front Panel
A
Carefully place the top cover with
threaded rods on top of washfountain
sprayhead .
B
Inside the pedestal assembly of the
washfountain (use front access), slide
the anchor plate onto the threaded rods
and secure anchor plate against bowl
using the wing nuts provided .
C
To install front panel, slip slot in bottom
of front pedestal panel over the lip on the
lower bracket,
D
Secure panel to upper bracket with
attached screw .
Summary of Contents for K-3363
Page 1: ...Spec Seq 72 S 1...
Page 15: ...Spec Seq 81 S 2...
Page 31: ...Spec Seq 90 WF 1...
Page 49: ......
Page 50: ...Spec Seq 94 MB 1...
Page 52: ...5431 West 164th Street Brook Park Ohio 44142 Spec Seq 96 189085...
Page 53: ...Spec Seq 96 189085...
Page 54: ...Spec Seq 96 189085...
Page 55: ...5431 West 164th Street Brook Park Ohio 44142 Spec Seq 96 189085...
Page 58: ...Cartridge Maintenance Repair Guide Spec Seq 98 361769...
Page 76: ...Cartridge Maintenance Repair Guide Spec Seq 98 361769...
Page 94: ...Spec Seq 100 SH 1...
Page 174: ...Spec Seq 112 SH 2...