TP-6865 4/14
27
Section 4 Communications
Setting
Range
Default
Notes
Modbus Enabled
True or False
True
Enable for network communication through the ethernet port.
Modbus Baud Rate
9600, 19200, 57600
19200
Baud rate in bits per second for serial communication between the
controller and a personal computer’s COM port.
Modbus Slave Address
001-247
0
Address for the RS-485 serial port (on the controller board).
Modbus Parity
Read only
None
Not adjustable.
Modbus Stop Bits
Read only
1
Not adjustable.
DHCP Enabled
True or False
False
Dynamic host communication protocol. Enable if required; check
with your local network administrator.
Static IP Address
See notes.
*
Obtain from your local network administrator. Every device on the
network must have a unique IP address.
Static Subnet Mask
See notes.
*
Obtain from your local network administrator.
All devices that communicate with each other on the same local
network must use the same subnet mask.
Static Default Gateway
See notes.
*
Obtain from your local network administrator.
DHCP Server
Read only
—
Displayed for information only.
Modbus TCP Unit ID
001-247
002
The unit ID is required for Modbus over TCP communication.
Modbus TCP Server Enabled
True or False
True
Enable (set to True) to enable TCP/IP communication (for example,
Ethernet communication).
MAC Address
Not Adjustable
Factory-
set
Hardware address, entered at the factory. Not adjustable.
* Do not use the factory settings for IP address, subnet mask, or default gateway. Obtain these settings from your local network
administrator.
Figure 4-9
Communication Parameters
Summary of Contents for Decision-Maker MPAC 750
Page 2: ......
Page 30: ...TP 6865 4 14 30 Section 4 Communications Notes ...
Page 39: ...TP 6865 4 14 39 Section 6 Accessories Figure 6 9 SPD Wiring Diagram GM89992 ...
Page 42: ...TP 6865 4 14 42 Section 6 Accessories Notes ...
Page 45: ...TPMPFP 6865 4 14 45 Notes ...
Page 46: ...TPMPFP 6865 4 14 46 Notes ...
Page 47: ......