156
12.
Object value export via XML
Make KNX objects XML readable
In the
Objects
tab click on the objects which you want to receive the current value by XML
request. Check the Export object
XML request from external PC
The XML request looks like this:
http://remote:[email protected]/cgi-bin/scada-remote/request.cgi?m=xml&r=objects
Parameters:
•
address
– object address (e.g. “1/1/1
″
)
•
name
– object name (e.g. “My object”)
•
data
– decoded object value (e.g 42 or “01.01.2012
″
)
•
datatype
– object datatype (e.g. 1 or 5.001) – standard KNX data types
•
time
– object update time (UNIX timestamp)
•
date
– object update time (RFC date)
•
comment
– object comment (e.g. “Second floor entry lights”)
•
tag
s
– optional array of object tags (e.g. “Light”, “Second floor”)
Note!
To get list of objects that have been updated after specific time you can pass an optional
“updatetime” parameter (UNIX timestamp format)
Summary of Contents for LogicMachine3 Re:actor
Page 10: ...10 Terminal connection schemes KNX TP...
Page 12: ...12 24V power supply...
Page 13: ...13 Analog inputs e g reed contact...
Page 14: ...14 Analog inputs 0 10V...
Page 15: ...15 Digital output...
Page 16: ...16 Resistive sensor input...
Page 17: ...17 Analog output...
Page 26: ...26 Make sure that bus status is Online press button in ETS...
Page 35: ...35 o Then minimize side bar by pressing on left arrow icon to make the map more visible...
Page 83: ...83 66 if err then 67 alert FTP upload failed s err 68 end...
Page 107: ...107...
Page 108: ...108 1 14 Help Documentation for scripting syntaxes is displayed in Help tab...
Page 126: ...126 Datapoints can be shown also in a way of table which can be later exported as CSV file...
Page 141: ...141...