53
www.kistlermorse.com
97-1129-01 Rev. D
14. Press the enter key to access the IOut Failsafe menu. The display looks like this:
FAIL-SAFe: *LO
(Asterisk indicates the current selection.)
If the displayed menu does not have the desired fail-safe, press the Up Arrow Key to display the next
page of the menu. Continue to press an Arrow Key until you see the desired selection (there are three
pages to the Fail-Safe Menu).
15. When the display shows the desired fail-safe, press the Enter Key. The display acknowledges the
selection and returns to:
45 IOuT FAILSAFe
16. The SVS2000 automatically enabled the current output (46 IOut Enable) when you entered values for
functions 41through 45 above. Press an Arrow Key to scroll to another menu or press the Gross or net
Key to return to Run Mode.
48 currenT adJST (adJuST)
This menu manually assigns counts-tomilliamps outputs for 0 mA, 4 mA, and 20 mA outputs to calibrate to
another device. Follow this procedure:
1. If the SVS2000 is in Run Mode, press the ‘4’ Key, ‘8’ Key, and Enter Key to access the menu tree. The
display shows:
48 CurrenT ADJST
2. Press the enter key to access this menu. The display shows:
ADJuST 0mA POInT
If the current output range is 4-20 mA, press the Up Arrow Key to display the second page of the menu.
The display shows:
ADJuST 4mA POInT
3. When the display shows the low current output for your application, press the Enter Key. The display
looks like this:
> 3600 cnts
note: If you set up 4-20 mA output, the SvS2000 ignores entries for 0 mA. Similarly, if you set up 0-20
mA output, the SVS2000 ignores entries for 4 mA.
4. Use the numeric or Arrow Keys to change the counts assigned to the current output if desired. Press the
enter key to save the value in memory. The display acknowledges the entry and returns to:
ADJuST XmA POInT
(‘4’ or ‘0’ is in place of ‘X.’)
5. Press the up Arrow key once or twice to proceed to Adjst 20mA Point. The display shows:
ADJST 20mA POInT
6. Repeat Steps 3, 4 for the 20 mA current output. After you adjust the 20 mA current output, the display
returns to:
ADJuST 20mA POInT
7. Press the Gross or net Key to return to Run Mode.
Summary of Contents for SVS2000
Page 1: ...SVS2000 Installation Operation Manual IOM97 1129 01 Rev D...
Page 2: ......
Page 10: ...6 97 1129 01 Rev D www kistlermorse com...
Page 11: ...7 www kistlermorse com 97 1129 01 Rev D...
Page 12: ...8 97 1129 01 Rev D www kistlermorse com...
Page 13: ...9 www kistlermorse com 97 1129 01 Rev D...
Page 14: ...10 97 1129 01 Rev D www kistlermorse com...
Page 20: ...16 97 1129 01 Rev D www kistlermorse com Figure 3 Wiring Diagram Current Output Card venture...