Chapter 3: Configuration and commissioning
92
KFP-A Series Installation Manual
To configure delayed output group activation:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Confirmations, and then select the output group to configure.
A list of the available output groups that allow alarm confirmation
configuration is displayed.
3. Select Active, and then select YES (alarm confirmation is required) or NO
(alarm confirmation is not required).
4. Select Alarm1, and then select the confirmation required (DEV, ZONE,
PANEL, or ALWAYS). Repeat this step for Alarm2.
If alarm confirmation is required then the output group is activated only when
both configured alarm confirmation states are detected during the
confirmation delay period.
Extinguishing output group confirmation requires two zones to be configured
for Alarm1 and Alarm2. See note below.
5. Select Delay, and then enter the confirmation delay in seconds (0 to 999).
6. Select EXTnode, and then enter the address of the extinguishing control
panel.
This field is only available when configuring confirmation for an extinguishing
output group.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Note
A remote extinguishing panel can be configured to receive extinguishing
preactivate and activate commands associated with the local extinguishing
output group confirmation.
When one of the two configured confirmation zones (Alarm1, Alarm2) enters into
alarm, the preactivate command is sent to the extinguishing panel (EXTnode).
When the second zone enters into alarm, the activate command is sent to the
extinguishing panel.
Assigning an output group to a programmable button
Note:
This option is not available for control panels in regional mode VdS 2540.
For fire alarm control panels, one output group can be assigned to the
programmable button and LED on the control panel interface for control and
indication. See Figure 1 on page 4 for the location of the programmable button
and LED.
For evacuation panels, up to seven output groups can be assigned to the
programmable buttons and LEDs. See Figure 2 on page 5 for the location of the
programmable buttons and LEDs
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......