Chapter 3: Configuration and commissioning
KFP-A Series Installation Manual
95
6. If required, enter a warning delay (in minutes and seconds) for sounder output
groups in applications using warning tones (second stage sounders).
A warning delay is only observed if the corresponding warning time is also
configured (see “Warning time” on page 100 for more information on this
option). The maximum warning delay value is 10 minutes.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Once a delay has been configured, it must be enabled.
Configured delays are only activated for alarms activated by a detector. Alarms
activated by a manual call point ignore any configured delays.
Configured delays can be enabled or disabled by sensitivity mode programming
(day/night mode), remote equipment by means of a programmed input, or the
user interface delay buttons.
By default, the control panel does not process delays when operating in night
mode. Remember that night mode can be activated by the day/night mode
schedule, the holiday calendar, or by remote equipment. For specific
applications, a delay in night mode can be configured if required. See “Additional
day/night mode settings” on page 43.
Use these options to configure, for example, activation of sounders and fire
routing with 2 minute delay for any zone in alarm in the fire network inside the fire
alarm panel zone range.
Notes
•
Global delay options only set the delays of the zones that are enabled to
activate the sounder or fire routing group. For example, if sounders and fire
routing activate for zone 1 with a delay of 10 seconds and for zone 5 with a
delay of 2 minutes, when selecting this option, sounders and fire routing will
activate with the same selected delay after alarms in zones 1 or 5 and will not
activate for all the other zones.
•
The Activate for all zones option allows the user to apply the delay to all
zones (including those previously configured not to activate the output group).
Per zone (sounder, fire routing, fire protection, or program)
Select Per zone to activate output groups with different delays (including no
activation) depending on which zone generated the alarm.
All outputs assigned to the output group activate depending on alarms in the fire
network, in the local range of zones of the panel, and with different delays.
For example, select this option to activate output group number 5 (sounder, fire
routing, fire protection, or program) with a delay of 10 seconds for a detector
alarm in zone 1 and with a delay of 2 minutes for a detector alarm in zone 5.
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......