KFP-A Series Installation Manual
123
Appendix A
Default configurations
The following table shows the settings for the default configuration of your panel.
Table 66: Default configurations
Description
Default setting
Power supply operation
230 VAC
Control panel ID
01
Day/night mode
Full day to day mode
Control panel network operation
Stand-alone
Network global commands
Yes
Network mask
0 (all panels excluded from the mask)
Repeater panel network operation Repeater
Repeater mask
All panels repeated
IP address
192.168.104.140
Subnet mask
255.255.255.0
Gateway
0.0.0.0
Port
2505
24V auxiliary
Not deactivated during reset, not deactivated when running
on batteries
Fault mask
All faults are reported
Sounders re-sound
Sounders re-sound
Expansion boards for repeater
panels
Network board is configured
Initial zone
1
Autosetup zone
All detectors, manual call points, and zone modules to the
initial zone
All sounders to output group 1 (sounders)
All relay/non-supervised outputs to output group 301
(program)
All extinguishing modules to output group 801
(extinguishing)
All inputs configured as technical alarm latched
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......