Chapter 3: Configuration and commissioning
KFP-A Series Installation Manual
89
Output groups
Select Output groups to configure the control panel output groups. Control panel
outputs must be assigned to output groups for activation.
An output group is a collection of outputs of the same type that activate and
deactivate at the same time (they are commanded simultaneously). Output
groups are identified by the output group number.
Outputs are assigned to the default output groups during autosetup (see
“Autosetup” on page 76).
Up to 300 sounder, fire routing, fire protection, extinguishing, and program output
groups can be configured (depending on group type).
Sounder output groups, fire routing output groups, and fire protection output
groups are controlled (and their status indicated) by the corresponding sounder,
fire routing, and fire protection buttons and LEDs on the front of the control panel.
Program output groups have no associated buttons or LEDs on the front of the
control panel but their status is displayed on the LCD.
The default control panel output groups are shown below.
Note:
This option is not available on repeater panels.
Table 52: Default output groups
Group number
Type
Description
1
SND
Sounder and supervised outputs.
301
PRG
Nonsupervised relay outputs. These outputs are assigned
to this group during autosetup.
801
EXTIN
Extinguishing device outputs. [1]
971
FR
Fire routing outputs. This group is only available on
control panels with the corresponding fire routing controls.
981
FP
Fire protection outputs. This group is only available on
control panels with the corresponding fire protection
controls.
991
ALARM [2]
Outputs activated when the control panel is in alarm
status.
992
FAULT [2]
Outputs activated when the control panel is in fault status.
993
DIS [2]
Outputs activated when the control panel is in disable
status.
994
TEST [2]
Outputs activated when the control panel is in test status.
[1] Extinguishing output groups are only activated with EN 54 type C alarm confirmation.
[2] These output groups are not configurable.
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......