Chapter 2: Installation
26
KFP-A Series Installation Manual
Figure 13: Overview of EN 54-13 fire system connections with a single Class A loop
1. 2010-FS-EOL end-of-line device
2. Fault indicating equipment
Connecting loops
Loop guidelines
For best results, follow these guidelines when connecting loops:
•
Install at least one isolator per loop (we recommend one for every 32
devices).
•
Keep loop cabling away from high-voltage cables (or any other source of
interference).
•
Star, stub, and T-tap configurations are not recommended.
•
Install loop devices with a high current consumption as close as possible to
the control panel.