Chapter 3: Configuration and commissioning
86
KFP-A Series Installation Manual
Type
Description
MCP
Manual call point alarm.
This input type can be used for connecting to aspirating detector Fire2
outputs.
PREAL
Prealarm (unlatched).
This input type can be used for connecting to aspirating detector Action
outputs.
RST
Activation resets the panel remotely. To reset again, the input must be
deactivated, and then activated again.
FLT
External fault. Activation generates a latched fault event indicated as an
external fault.
DAY
Day mode. When this input is activated, the control panel switches to
day mode until the next scheduled night mode change (or until the
output is deactivated).
NIGHT
Night mode. When this input is activated, the control panel switches to
night mode until the next scheduled day mode change (or until the
output is deactivated).
FOS
Fault Warning Output Open Supervision. By using a 2010-FS-EOL end-
of-line device, the control panel can supervise the open circuit condition
of the Fault Warning output.
FRAK1
Fire routing acknowledgement (type 1). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 100 seconds of fire routing activation, the control panel
reports a fire routing fault.
FRAK2
Fire routing acknowledgement (type 2). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 240 seconds of fire routing activation, the control panel
reports a fire routing fault.
FPAK1
Fire protection acknowledgement (type 1). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 100 seconds of fire protection
activation, the control panel reports a fire protection fault.
FPAK2
Fire protection acknowledgement (type 2). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 240 seconds of fire protection
activation, the control panel reports a fire protection fault.
FP_FT
Fire protection fault. Used to indicate remote faults in fire protection
equipment.
FBFSD
FBF sounders disable. The input is configured to interface to remote
FBF equipment to disable or enable sounders.
UKSB
British school class change. Activation activates sounders for school
class change indication.
MSP
Manual call point alarm (sprinkler).
MHA
Manual call point alarm (“hausalarm”).
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......