Chapter 3: Configuration and commissioning
KFP-A Series Installation Manual
97
General delays
Select General delays to configure region-specific investigation times or
advanced delay options.
Configurable options for general delays are shown in the table below.
Table 57: Configurable options for general delays
Field
Description
InvMode
Investigation mode. Enables regional investigation time modes
(maximum acknowledgement time, extended fire routing delay).
Time
Investigation time. Configures regional investigation time delays
(maximum acknowledgement time, extended fire routing delay).
Inv_Ack
Investigation time on acknowledgement. If checked, any
configured investigation time starts when the alarm is
acknowledged. If unchecked, any configured investigation time
starts when the alarm is detected.
WrnTime
Warning time. Configures the warning time when the control
panel is configured to use a warning tone for a second stage
sounders application. For standard applications with no warning
tone requirement, this time must be 0.
WrnT_4E
Warning time (extended). If checked, the warning tone (where
configured) will change to the evacuation tone only if a manual
call point alarm is detected.
SdSilDT
Sounder silence disable time. Disables silencing sounders with
the Sounder Start/Stop button for a preconfigured time when a
sounder delay is running.
To configure general delays:
1. Select Field setup from the Main menu, and then select Activation
configuration.
2. Select General delays.
3. Select Investigation mode, and then select the type of investigation mode
required.
See “Investigation mode” on page 98 for more information on this option.
4. If an investigation mode is selected, select Time, and then enter the time
value (in seconds).
Check Inv_Ack if you want any configured investigation time to start counting
down when the alarm is acknowledged (by default any configured
investigation time starts when the alarm is detected).
See “Investigation time” on page 99 for more information on this option.
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......