Chapter 3: Configuration and commissioning
KFP-A Series Installation Manual
99
Setting
Description
FREXT_ACK
Extended fire routing delay (typically for Scandinavia).
The configured fire routing delay starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the configured fire routing delay
(by pressing the Panel Silence button), then the extended fire
routing delay becomes the active delay.
If the alarm is not acknowledged during the configured fire routing
delay (by pressing the Panel Silence button), then the extended fire
routing delay is not activated.
FREXT_SND [1]
Extended fire routing delay (typically for Holland).
The standard fire routing delay starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the configured fire routing delay
(by pressing the Sounders Start/Stop button), then the extended fire
routing delay becomes the active delay.
If the alarm is not acknowledged during the configured fire routing
delay (by pressing the Sounders Start/Stop button), then the
extended fire routing delay is not activated.
FREXT_VDS [2]
Extended fire routing delay (typically for Germany).
The configured fire routing delay starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the configured fire routing delay
(by pressing the Investigation Time button), then the extended fire
routing delay becomes the active delay.
If the alarm is not acknowledged during the configured fire routing
delay (by pressing the Investigation Time button), then the extended
fire routing delay is not activated.
[1] Sounder delay must be configured as 0 seconds for this option.
[2] The Investigation Time button is only available on selected models operating in VdS 2540
mode.
Investigation time
Select Investigation time to configure the duration (in seconds) of the
investigation time for the configured investigation mode. Minimum, maximum,
and default values for each mode are shown in the table below.
Table 59: Investigation time values per mode
Investigation mode
Minimum
Maximum
Default
Manual acknowledgement time
30 seconds
See note [1]
60 seconds
Extended fire routing delay
See note [2]
600 seconds
60 seconds
[1] The maximum value must be less than the minimum delay to activate a sounder or fire
routing group.
[2] The minimum value must be greater than the maximum activation delay for any fire routing
group.
Summary of Contents for KFP-AE1(-S)
Page 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Page 6: ...iv KFP A Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Page 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Page 114: ......
Page 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Page 148: ......