RC04-PCR-LA
Operation Method 4-19
• The status signal outputs while the period of time set for the
T2, T3 and T4 (if T2=T4=0, this case applies T3). For detail
of the output terminal, see “
4.3.6 Sequence Operation
Sequence operation is the action of retrieving and outputting in
sequence the settings of combinations of output voltage, frequency,
time, and other factors that have been stored in advance. This function
allows the AC power supply to perform automatic operation.
Sequence operation is accomplished by setting sequence content in
the sequence setting mode, and then executing operation in the
sequence execution mode.
Fig.4-7
Example of Sequence Operation
The sequence setting mode has the four displays. There are 10
sequence setting items, including address designation, AC voltage,
DC voltage, specifying ramp for AC voltage and frequency change
characteristics (see the Description on page 4-22), time, and wave-
form. Set the desired items from among these.
The setting items contained on each display are as shown in Fig. 4-8.
In addition, the validity/invalidity of set values in sequence operation
is determined by the output mode used to run a sequence. In Fig. 4-8,
the relationship between the validity and the output modes is also
shown.
DESCRIPTION
Voltage change
Frequency change