3. Installation

General instructions for installation of 
backwater valves

According to DIN EN 12056 it is not allo-
wed to connect all drainage fixtures from 
a building (including those located above 

the backwater level – ground level) through 
a backwater valve.  The reason being that 
when the backwater flap is in the closed 
position due to backwater / flooding no 
wastewater will be able to flow through the 

backwater valve meaning that the building’s 
own wastewater will flood out of the lowest 
drainage fixture connected (normally in the 
basement) to the backwater valve.

Incorrect installation of a backwater valve

Correct installation of a backwater valve

DIN EN 12056 specifically states that only drainage fixtures below 
the backwater level may be connected to a backwater valve. All 
drainage fixtures above the backwater level should be drained 
through a separate pipe directly into the sewer (not through the 
backwater valve).  This means that the home / building must be 
equipped with separate drainage pipes.

A building’s wastewater from above the backwater level (above 
ground level) can drain freely into the sewer at all times.  During 
backwater the higher head / pressure of wastewater above the 
backwater level will force its way into the surcharged sewer and will 
not flood the basement / lower levels.  Rainwater drainage pipes 
must not be connected to a backwater valve.

Right

Backwater valve

 Sewer

Backwater valve

Sewer

Backwater 
level

Wrong:

Backwater 
level

Please note:

DIN EN 12056 requirements should be clo-
sely followed during the planning and ins-
talling of drainage pipes!  Vertical draina-
ge pipes connected to a backwater valve 
should not be connected directly in front 
of or directly behind the Staufix FKA but 
should be connected at least 1 meter before 
or after the backwater valve – this is the so 
called ‘wastewater calming’ area. A back-
water valves should also be installed so that 
access to the valve for service, maintenan-
ce or repair is possible.

Caution:

 Make sure that the backwater 

valve is installed in the proper direction and 
is not installed backwards.  KESSEL back-
water valves are equipped with flow direc-
tion arrows to make sure that the valve is 
installed in the proper direction.

3.1 Concrete slab installation of  Stau-
fix FKA

The Staufix FKA body should be installed 
perfectly horizontal (please see illustration 
1).  The electrical cables for the backwater 
flap motor and the optical sensor should 
be laid in a conduit (minimum conduit size 
DN 50 (2 inch), KESSEL recommends not 
using 90 degree bends – maximum 45 de-
gree bends) (see Illustration 2).  This con-
duit should be connected to the conduit 

connection hole on the side of the Stau-
fix FKA body. The included gasket should 
be placed into the recessed area of the 
housing (as shown in illustration 3) and then 
the upper portion of this gasket should be 
lubricated.  The included upper section can 
then be inserted into the housing as seen 
in illustration 4. This upper section can be 
tilted up to 5 degrees and can be rotated 
to match floor / tile patterns.  It can also 
be vertically adjusted to meet the required 
cover installation height. After adjusting the 
upper section make sure that the gasket 
between housing base and upper section 
is still in the proper position.

Caution:

 In the case that a shallow instal-

lation is required in a concrete floor slab it 
may be necessary to shorten the upper sec-
tion which can be done by sawing off the 
required lower portion of the upper section.  
It is important that when the upper section 
is in its final position that the conduit access 
still is free so that in the future electrical 
cables can be pulled out or insert into the 
conduit as required (see Illustration 5). 

Provide a cable tube for later retrofitting. If 
this cable tube has to be installed in the 
upper section, drill a hole with the KESSEL 
hole saw (article number 500101) or a stan-
dard Ø 60 mm hole saw and put in the pipe 
sealing gasket (article number 850114)

.

The second gasket must be inserted in the 
cover. Important is that the sealing lip and 
centering tip are pointing up. The centering 
tip is to be inserted in the appropriate reces-
sed area as seen in illustration 5. During in-
stallation the valve should remain clean and 

DN50

Ill. 1

Ill. 2

Summary of Contents for 84000S

Page 1: ...tromausfall Bei R ckstau automatische Verriegelung Einfaches Auswechseln von Verschlei teilen Integrierter Einfachr ckstauverschluss f r stromlosen Betrieb w hrend der Bauphase Optimale Rohrreinigung...

Page 2: ...f die Anlage auf keinen Fall in Betrieb genommen wer den bzw ist umgehend abzustellen Zur Aufrechterhaltung der Betriebsf hig keit ist die Anlage entsprechend DIN EN 13564 zu inspizieren und zu warten...

Page 3: ...e en Sie erst bei Inbetriebnah me des KESSEL R ckstauautomaten Staufix FKA die elek trischen Anlagen komponenten Mo tor Son de und Schalt ger t an Bis da hin sind die se Anlagen komponenten entspreche...

Page 4: ...tte Der Grundk rper des KESSEL Staufix FKA ist waagrecht auszurichten Abb 1 F r den Anschluss der elektrischen Lei tungen von Sonde und Antriebsmotor ist bauseits ein Ka belleerrohr mind DN 50 KESSEL...

Page 5: ...e Be sch digung der Bauteile zu verhindern Zum Abnehmen der Schutzhaube ist gleichzeitig an beiden Klemmen einer Seite leicht zu ziehen Vor Demontage des schwarzen Unterteiles der Schutz haube sind Zu...

Page 6: ...ck ist ggf auf die erforderliche H he zu k rzen KESSEL Pumpfix F Staufix FKA Staufix SWA Controllfix Dichtungsset Art Nr 83075 Verl ngerungsst ck Art Nr 83070 BWS BWS Unterbeton Fliesen Estrich D mmun...

Page 7: ...den eine R ckstaugefahr muss ausgeschlossen sein Dabei ist folgendes durchzuf hren Entfernen von Schmutz und Ablage rungen Pr fen von Dichtungen und Dichtfl chen auf einwandfreien Zustand ggf Austausc...

Page 8: ...nicht mehr als 500 ccm Wasser nach gef llt werden muss Nach der Pr fung den Notverschluss 3 wieder ffnen Den Trichter 2 entfernen und die Verschlussschraube 1 mit dem Dichtring in den Deckel einschrau...

Page 9: ...nalit t pr fen Beide Klappen pr fen sie m ssen beide auf betriebsbereiten Zustand ge stellt sein Abb 15 4 Inspektion und Wartung 4 5 Funktion des Notverschlusses Verriegelungsstellung Abb 16 vollst n...

Page 10: ...perational even during power outages Automatic backwater flap closure during backwater Staufix FKA also offer powerless backwater protection during the building phase no power supply to building Upgra...

Page 11: ...he power source and no longer operated In order to insure proper condition and operation of the system it should be in spected and maintained according to DIN EN 13564 We recommend that a service and...

Page 12: ...should not be connected until the system is commissioned after the major const ruction phase of the building is complete It is important that the electrical compo nents of the Staufix FKA contained i...

Page 13: ...installed in the proper direction and is not installed backwards KESSEL back water valves are equipped with flow direc tion arrows to make sure that the valve is installed in the proper direction 3 1...

Page 14: ...to the system This protected cover is not water tight To remove the protective cover simple lift both clips on one side of the cover Before the black lower part of the protective hood is dis mantled t...

Page 15: ...heights requirements KESSEL Pumpfix F Staufix FKA Staufix SWA Controllfix Groundwater protection set 83071 Extension section Article Number 83070 BWS BWS Unterbeton Fliesen Estrich D mmung Betonboden...

Page 16: ...ent of the two flaps as well as the manual clo sure lever lubricate if necessary Check to make sure the system is water tight and in proper operating condition by performing the functi on sealing test...

Page 17: ...d to keep the water level at 10cm If no more than 500ml of water was required to keep the water level at the 10cm mark during the 10 minute test then the valve is considered tight After the test re op...

Page 18: ...manually ope rated backwater flap Final step is to make sure both the motorized and the manually operated backwater flap are in the open position 4 5 Purpose of the emergency closure flap The emergen...

Page 19: ...joints Fiabilit de service m me en panne de courant Verrouillage automatique en cas de re foulement Facilit d change des pi ces d usure Simple clapet anti refoulement int gr pour une exploitation sans...

Page 20: ...cas tre mise en service et ou doit tre imm diatement arr t e Pour conserver l installation en tat d ex ploitation il faut la visiter et l entretenir conform ment la DIN EN 13564 Nous recommandons de p...

Page 21: ...at de livraison Veuillez ne raccorder les composants de l automate de refoulement Staufix FKA moteur sonde et bo tier de commande que lors de la mise en service D ici l stockez les composants de l ins...

Page 22: ...nce avec le au mur pour les op rations de maintenance 3 1 KESSEL Staufix FKA pour pose dans la dalle de fondation Le corps principal du KESSEL Staufix FKA doit tre pos l horizontale voir figure 1 Le r...

Page 23: ...tection pour viter un endommagement des pi ces apr s la mise en service Pour ter le capot de protection il faut tirer l g rement en m me temps sur un c t des deux vis de serrage Avant le d montage de...

Page 24: ...requise KESSEL Pumpfix F Staufix FKA Staufix SWA Controllfix Jeu de joints article n 83075 Pi ce de rallonge article n 83070 BWS BWS Unterbeton Fliesen Estrich D mmung Betonboden Fliesen Estrich D mmu...

Page 25: ...uivants doivent tre ex cut s Retirer la salet et les d p ts Contr ler si les joints et les port es de joint sont en bon tat si n ces saire proc der l change des joints voir figures 9 11 Contr ler la m...

Page 26: ...si pendant ce temps il ne faut pas rajouter plus 500 ccm d eau R ouvrir apr s le contr le de la vanne batardeau 3 Retirer la tr mie 2 et visser la vis de fermeture 1 avec la bague d tan ch it dans le...

Page 27: ...ifier les deux cla pets ils doivent tre mis tous les deux en tat pr t fonctionner Fig 15 4 Inspection et maintenance 4 5 Fonctionnement de la vanne batardeau Position de verrouillage figure 16 vanne b...

Page 28: ...in tubazioni continue Sicurezza di funzionamento anche in caso di interruzione di corrente Bloccaggio automatico in caso di riflusso Facile sostituzione dei particolari soggetti a usura Chiusura antir...

Page 29: ...mediatamente Per conservare la funzionalit l impianto deve essere ispezionato e manutenuto conf DIN EN 13564 Consigliamo di stipulare il contratto di ma nutenzione accluso con l azienda instal latrice...

Page 30: ...tto della consegna Solo alla messa in funzione dell impianto antiriflusso automatico Staufix FKA KES SEL collegare le componenti elettriche dell impianto motore sonda e centrali na Fino a quel momento...

Page 31: ...parete per i lavori di manuten zione 3 1 Staufix FKA KESSEL per il montaggio nella piastra di fondazione Il corpo base dello Staufix FKA KESSEL deve essere allineato orizzontalmente ill 1 Per l allac...

Page 32: ...ornito con una calotta di protezione Per togliere la calotta tirare contemporanea mente i due dispositivi di fissaggio di un lato Prima dello smontaggio della parte inferiore nera della calotta di pro...

Page 33: ...rolfix KESSEL Set di guarnizioni n art 83075 Prolunga n art 83070 BWS BWS Unterbeton Fliesen Estrich D mmung Betonboden Fliesen Estrich D mmung Betonboden Schutzbeton Abdichtung 1 2 3 2 1 Esempio di m...

Page 34: ...i sporco e depositi controllo dello stato di guarnizioni e superfici di tenuta eventualmente sostituzione delle guarnizioni vedi ill 9 11 controllo della meccanica degli or gani di tenuta mobili event...

Page 35: ...re rabboccati pi di 500 cm3 d acqua Dopo il controllo riaprire il dispositivo di chiusura d emergenza 3 Togliere l imbuto 2 e avvitare nel coperchio il tappo a vite 1 con l anello di tenuta Riaprire l...

Page 36: ...arsi nello stato pronto per l uso 4 Ispezione e manutenzione 4 5 Funzione del dispositivo di chiusura d emergenza Posizione di bloccaggio ill 16 disposi tivo di chiusura d emergenza completa mente chi...

Page 37: ...buisleidingen Bedrijfsveiligheid ook bij stroomuitval Bij terugstroming automatische blokkering Eenvoudig vervangen van aan slijtage onderhevige onderdelen Ge ntegreerde enkelvoudige terugs troom afs...

Page 38: ...mag de installatie in geen geval in bedrijf worden genomen of moet direct worden uitgezet Voor handhaving van de functionali teit dient de installatie conform DIN EN 13564 te worden ge nspecteerd en...

Page 39: ...nd Sluit a u b pas bij inbedrijfstelling van de KESSEL automatische terugstroombe veiliging Staufix FKA de elektrische in stallatiecomponenten motor sonde en schakelapparaat aan Deze installatie compo...

Page 40: ...van de automatische terugstroombeveili ging moet voor onderhoudswerkzaamheden op voldoende afstand tot de wand worden gelet 3 1 KESSEL Staufix FKA voor inbouw in de grondplaat Het basislichaam van de...

Page 41: ...wordt geleverd met een beschermkap om te voorkomen dat onderdelen na de inbedrijfstelling beschadigd raken Om de beschermkap weg te nemen moet tegelijkertijd aan beide klemmen van n kant worden getrok...

Page 42: ...fix F Staufix FKA Staufix SWA Controllfix Pakkingset art nr 83075 Verlengstuk Art nr 83070 BWS BWS Unterbeton Fliesen Estrich D mmung Betonboden Fliesen Estrich D mmung Betonboden Schutzbeton Abdichtu...

Page 43: ...stroming moet uitgesloten zijn Hierbij moet het volgende worden uit gevoerd Verwijderen van vuil en afzettingen Controleren of pakkingen en af dichtvlakken in perfecte staat verkeren evtl vervangen va...

Page 44: ...in deze tijd niet meer dan 500 ccm water moet worden bijgevuld Na de controle de noodafsluiter 3 weer openen De trechter 2 verwijderen en de sluitschroef 1 met de afdichtring in de deksel schroeven D...

Page 45: ...e functionaliteit Beide kleppen controleren zij moeten allebei gereed voor bedrijf zijn gezet 4 Inspectie en onderhoud 4 5 Functie van de noodsluiter Vergrendelingsstand afb 16 volledig gesloten nooda...

Page 46: ...omatyczne blokowanie przy przep ywie zwrotnym atwa wymiana cz ci eksploatacyjnych Zintegrowany jednoklapowy zaw r zwrotny gwarantuj cy dzia anie podczas fazy budowlanej bez potrzeby pod czania do napi...

Page 47: ...ia urz dzenia nie wolno w cza lub trzeba je natychmiast wy czy Wceluzachowaniasprawno ciurz dzenia nale y przeprowadza prace inspekcyjne i kon serwacyjne zgodnie z PN EN 13564 Zalecamy zawarcie za czo...

Page 48: ...uru chomienie rozdzia 5 Stan w momencie wydania Elektryczne komponenty urz dzenia pompa sonda urz dzenie sterownic ze nale y pod cza dopiero przy rozru chu automatycznego zaworu zwrotnego KESSEL Stauf...

Page 49: ...o nale y zwr ci uwag na wystarczaj cy odst p od ciany konieczny do wykony wania prac konserwacyjnych 3 1 KESSEL Staufix FKA do zabu dowy w p ycie pod ogowej Korpus KESSEL Staufix FKA nale y wypoziomow...

Page 50: ...arczane z pokryw ochronn aby po rozruchu unikn uszkodze nia podzespo w W celu zdj cia po krywy ochronnej jednocze nie nale y poci gn oba zaciski po bokach Przed demonta em czarnej cz ci dolnej po kryw...

Page 51: ...na raz mo na dostosowa wysoko ko nierza Nasadk mo na w razie potrzeby skr ci do potrzebnej wysoko ci 1 KESSEL Pumpfix F Staufix FKA Staufix SWA Controllfix 2 Zestaw uszczelek nr art 83075 3 Przed u k...

Page 52: ...zwrotnym Nale y przy tym 1 Usun zanieczyszczenia i osady 2 Sprawdzi uszczelki i powierzchnie uszczelniane czy nadal s w niena ganny stanie wraziekonieczno ci wymieni uszczelki patrz rys 9 11 3 Skontr...

Page 53: ...uzupe ni do pierwotnej wysoko ci Zaw r zwrotny mo na uzna za szczelny je li w tym czasie uzupe ni si nie wi cej ni 500 ml wody Po wykonaniu kontroli zamkni cie awaryjne 3 ponownie otworzy Lejek 2 usun...

Page 54: ...yciskiej Kon trola Sprawdzi obie klapy obie musz znajdowa si w stanie gotowym do pracy 4 Inspekcja i konserwacja 4 5 Funkcja zamykania awaryjnego Pozycja ryglowania rys 16 w pe ni zamkni te zamykanie...

Page 55: ...5 lmpermeabilita all acqua I Waterdichtheid Wodoszczelnosc Vandtrethed 16 Superata Geslaagd I przekazywane Oversteget 17 lmpermeabilita agli odori Geurdichtheid Szczelnosc zapachu Lugt trethed 18 Effi...

Page 56: ...56...

Reviews: