- 59 -
Does the cold-air come out
of the top of the main duct?
Check the
Damper
itself
No
Yes
After reset the unit
, take steps to PWB as
follows for temperature compensation.
1. In the case of EBR419564
: Compensate with Jump wire cutting
* Cutting of jumper wire
Enter the TEST 2 MODE
Does not cold-air come out
of the top of the main duct?
Check the
Damper
itself
Yes
No
Checking Damper itself
Is the resistance Values
between (1) & (4), (2) & (3)
like as below?
Replace
Damper
(Position
No: 120A)
No
Yes
(1)RD
(3)BL
(4)YL
(2)WH
Resistance of Damper
Test Point
(1) To (4)
(2) To (3)
Result
373 ~ 456
Ω
373 ~ 456
Ω
JUMP WIRE
Cutting both jumpers affords a 2
。
temperature compensation
Temp. Compensation
-1.0 deg
-1.0 deg
JCR3
JCR4