51

ServoA

 

Operation Manual

Diagnostics

ID no.: LDS-O-SA-EN-202103

Display

Software code

Error 

number

Error description

E-OC

Current overload

0

Current overload due to:
1. Incorrect parameter setting
2. Short, earth fault or insulation fault
3. Internal device defect
Remedy:
1. Check parameters of control circuits
2. Check installation

1

Ixt-shut-off below 5 Hz to protect power stage.
Reduce load

43

Power stage protection initiated, maximum allo-

wed motor power exceeded. The value depends 

on DC-link voltage and heat sink temperature.
1. Check operating conditions of device
2. Reduce load

46

Current overload shut-off after wiring test.Detec-

ted short, earth fault or insulation fault.
1. Check installation
2. Check motor insulation

48

Current overload detected
1. Adverse parameter adjustment
2. Short circuit, earth fault or bad isolation in active 

state
3. Internal device error
Remedy:
1. Check parameter adjustment of control circuit
2. Check installation
3. Please contact your service provider if this error 

occurs again

49

Same as above

50

Internal error while current overload monitoring
1. Switch off/on device
2. Please contact your service provider if this error 

occurs again

Display

Software code

Error 

number

Error description

E-OV

Voltage overload

1

Voltage overload due to:
1. Braking chopper overload (braked too long or too 
much)
2. Mains poer overload
Remedy:
1. Set DECR ramp parameter lower, use ext. braking 
resistor or chopper
2. Adjust mains voltage

E-OLM

Motor overload

47

Ixt-shut-off to protect motor (permissible current/time 
area exceeded)
1. Check parameter setting of motor protection
2. Reduce load
3. Use higher-powered motor

E-OLI

Driver overload

48

I^2xt-shut-off to protect power stage (permissible cur-
rent/time area exceeded)
1. Reduce load
2. Use higher-powered motor

E-OTM

Overheating motor 

46

Short circuit in motor temperature PTC
1. Check cabling of motor PTC

47

Overheating motor (PTC in motor tripped) due to:
1. Temperature sensor not connected or incorrect para-
meter setting
2. Overload of motor
Remedy:
1. Allow motor to cool down
2. Connect temperature sensor or check adjustment
3. Use a higher-powered motor 

Summary of Contents for ServoA SA52.0100

Page 1: ...ServoA Operation Manual Servo controllers 2 2 A 20 A ...

Page 2: ...tomers with a higher performance of drive ability to meet the demands of improvements Through ServoA and other new products KEBA will continuously develop technical ad vantages and contribute to modernization of manufacture of Chinese equipment We reserve the right to make technical changes The content of our documentation was compiled with the greatest care and attention and based on the latest i...

Page 3: ...ou kindly to read this Operation Manual thoroughly beforehand Step Action Comment 1 This Operation Manual will enable you to install and commission the ServoA drive system very quickly and easily Quick start guide 2 Simply follow the step by step tables in the various sections And away you go 1 1 Safety 2 2 Mechanical installation 3 3 Electrical installation 4 4 Comissioning 5 5 Diagostics A A App...

Page 4: ...Note means when power stage switching frequency is 4KHz 1 If braking power of motor is larger and the integrated braking resistor can t get rid of excess energy then external braking resistor should be connected 2 Standard without internal braking resistor and EMC filters with EtherCAT It can be connected with resolver and high resolution encoder 3 The motors match to BG5 please consult with KEBA ...

Page 5: ...n where they are placed without text such as next to a connection diagram Warnings see also section 1 1 Attention Misoperation may result in damage to the drive or malfunc tions Danger from electrical tension Improper behaviour may endanger human life Danger from rotating parts Drive may start up automatically Hints Tips Note Useful information or reference to other documents 1 Step Action in a se...

Page 6: ...6 ServoA Operation Manual ID no LDS O SA EN 202103 Space for your own notes ...

Page 7: ...nnection 28 3 10 1 Encoder interface X4a 30 3 10 2 Encoder interface X4b 31 3 11 Motor connection 33 3 11 1 Connection to LSM motors 34 3 11 2 Electronic overload protection for the motor 35 3 11 3 Switching in the motor cable 35 3 12 Braking resistor RB 35 3 12 1 Protection in case of braking chopper fault 35 3 12 2 Design with integrated braking resistor 35 3 12 3 Connection of an external braki...

Page 8: ... encoder 47 4 3 4 User log on 48 4 3 5 Jog mode Manual mode 48 4 4 _ALError messages 49 5 Diagnostics 50 5 1 Device states 50 5 2 Error codes and information 50 6 Functional torque off former STO 60 6 1 Definition of terms 60 6 1 1 Overview of functional torque off connections 60 6 1 2 Wiring and commissioning 61 7 UL certification 62 A Appendix 64 A 1 Current capacity of ServoA 64 A 2 ServoA ambi...

Page 9: ...ion against magnetic and or electromagnetic fields during installa tion and operation Persons fitted with heart pacemakers metallic implants and hearing aids etc must not be allowed access to the following areas Areas where drive systems are installed repaired and operated Areas where motors are installed repaired and operated Motors with permanent magnets pose a particular hazard NOTE If it is ne...

Page 10: ...viour may endan ger human life Death or serious injury will occur Danger from rotati ng parts Drive may start up automatically Death or serious injury will occur Table 1 2 Explanations of warning symbols 1 2 Intended use ServoA drive controllers are components designed solely for vertical installation in sta tionary electrical systems or machines When installed in machines the compliance with EN 6...

Page 11: ...nnel and machinery and to maintain the function capabil ity of the machine or system concerned and must be observed The function of an emergency off system does not necessarily have to cut the power supply to the drive To protect against danger it may be more beneficial to maintain individual drives in operation or to initiate specific safety sequences Execution of the emergency stop measure is as...

Page 12: ... a temperature cut out occurs the cooling condi tions must be improved Air flow min 1 2 m s 2 Mechanical installation 2 1 Notes for operation Please be sure to avoid penetration of damp into the device aggressive or conductive substances in the immediate vicinity drill chippings screws or foreigh bodies dropping into the device ventilation openings being covered over as otherwise the device may be...

Page 13: ...750 SA54 0900 Weight kg 1 1 5 2 65 4 9 B width 55 90 H height 209 289 T depth 145 190 234 234 A 27 5 C 225 305 313 D 4 8 E Direct butt mounted F 100 G 300 H1 235 318 324 All Dimensions in mm 1 Without terminals connectors 2 Take into account the bend radius of the connecting cables Table 2 2 Dimensions of ServoA C C1 A B D H1 T H G F F E Figure 2 2 Mounting pitch wall mounted mm Figure 2 1 Dimensi...

Page 14: ...ors should be at least 0 2 metres away from process controlled assemblies Supplementary information can also be found in the relevant connection description 3 Electrical installation 3 1 Notes for installation ATTENTION Qualified personnel Installation must only be carried out by qualified electricians who have under gone instruction in the necessary accident prevention measures During installatio...

Page 15: ...No Designation D1 D2 D3 D4 D5 D6 7 segment display H1 LED display PE Protective conductor connection T1 T2 T3 T4 Button X1 Power connection X2 Connection of control supply Uv X3 AC mains connection X4a Encoder interface Resolver Hiperface TTL Sincos X4b Encoder interface Endat2 1 SSI TTL sin cos for speed and position control X5 EtherCAT communication interface SA5x xxxx xx3x CANopen communication...

Page 16: ...rvoA Operation Manual ID no LDS O SA EN 202103 Electrical installation 3 3 Overview of connections Figure 3 2 1 Overview of connections for ServoA BG2 BG4 Figure 3 2 2 Overview of connections for ServoA BG5 ...

Page 17: ... via the encoder cables X4a or X4b Table 3 2 Key to connection diagram 3 4 Effective EMC installation 3 4 1 Interference immunity of drive controllers Atte ntion This is a restricted availability product in accordance with IEC 61800 3 This product may cause radio interference in domestic environ ments in such cases the operator may need to take appropriate counter measures Conducted emission Exter...

Page 18: ...minimum components required A Backing plate with cable ducts B ServoA C Mains filter D Line reactor E Distributor rail for AC power supply and control supply 24 V DC The layout and cabling are based on the instructions set out in section 3 1 Notes for installation on page 14 The numbered red arrows refer to four very important detailed notices presented on the following pages ...

Page 19: ...amp supplied NOTE Ready made up motor cables are available for KEBA servomotors Fordetails refer to the Servomotors order catalogue Figure 3 4 Specimen setup Detail 1 Motor cable X1 Detail 2 Control supply At the control supply connection X2 Secure the second of the two supplied shield connection plates by the screw to the mount on the bottom of the unit Ensure the plate contacts across a wide are...

Page 20: ...e output of the mains filter and at the AC mains connection X3 Connect the wire strands at the output of the mains filter directly to the AC mains connection X3 of the ServoA The strands must not be extended so the mains filter should be installed correspondingly close to the ServoA But be sure to maintain the necessary minimum clearance see table 2 2 on page 12 Fix the strands to the shield conne...

Page 21: ...age PELV Protective Extra Low Voltage 3 5 Protective conductor connection Step Action PE mains connection to DIN EN 61800 5 1 1 Ground each of the drive controllers Connect terminal in star configura tion and across a wide area to the PE rail main ground in the switch cabinet Rules for the PE terminal as leakage current 3 5 mA Use protective conductors with the same cross section as the mains powe...

Page 22: ... 24V DGND Endat 2 1 SSI TTL Sincos etc X4b V_μP GND_μP PE 1K6 1K6 1K6 1K6 DGND PE PE Figure 3 9 2 ServoA BG5 electrical isolation method GND_μP GND_μP ENPO X8 10 RSH Reslover Hiperface TTL Sincos etc X4a V_μP Master and Simulation X7 Master Simulation Ethercat X5 AD X8 22 AD X8 23 ISA_00 ISA_01 GND_μP X8 11 AGND GND_μP V_μP DA GND_μP X8 24 OSA_00 GND_μP X8 12 10 5V V_μP X8 8 OSD_00 X8 21 RSH X8 20...

Page 23: ...e checked to ensure no voltage is connected 3 7 Connection of supply voltages The voltage supply to the ServoA is separate for the control and power sections The control supply should always be connected first so that the device can be parameter ized with DriveManager 5 and above all set to the correct power supply ATTENTION Only when the mains voltage has been set and the ServoA restarted if the ...

Page 24: ...lectrical stress is approx twice as high Clearances and creepages to EN 61800 5 1 are no longer maintained Connection of the drive controllers by way of a mains choke is mandatory where the drive controller is used in applications with disturbance variables cor responding to environment class 3 as per EN 61000 2 4 and above hostile industrial environment in the case of single phase mains supply fo...

Page 25: ...section mm2 Max mains fuse class gG A with mains choke 4 uK without mains choke SA52 0075 3 0 4 2 2 5 16 SA52 0100 5 0 7 0 2 5 16 SA52 0150 6 0 8 4 2 5 16 SA52 0200 8 0 11 2 4 20 SA54 0075 2 0 2 8 2 5 6 SA54 0100 2 5 3 5 2 5 16 SA54 0150 3 5 4 9 2 5 16 SA54 0200 4 5 6 3 4 16 SA54 0300 6 5 9 1 4 16 SA54 0500 12 16 8 6 32 SA54 0750 16 22 4 6 40 SA54 0900 20 28 6 40 Table 3 3 Connected load and mains...

Page 26: ...6 3 8 Control connections Step Action Comments 1 Check whether a complete device setup is already available i e whether the drive has already been configured 2 If this is the case a special control termi nal assignment applies Please contact your project engineer to obtain the terminal assignment 3 Choose a terminal assignment Initial commissioning 4 Wire the control terminals with shielded cables...

Page 27: ...ort circuit 24 V DC DGND but device may briefly shut down Auxiliary voltage output UH to feed the digital control inputs UH UV ΔU ΔU typically ap prox 1 2 V no destruction in case of short circuit 24 V DGND but device may briefly shut down Imax 200 mA in sum with X8 7 Yes X8 7 Digital ground DGND X8 13 Reference ground for 24 V DC Yes X8 19 Table 3 4 Specification of control connections X8 3 9 USB...

Page 28: ...ti turn encoder with HIPERFACE interface e g LSML08 075 2F 002 ELH2 D15M H X4 Table 3 5 Variants of motors encoder type and encoder cable 3 10 Encoder connection Encoder connection X4 is located on the top of the unit Encoder connection of LSM motor Please use the ready made up motor and encoder cables from KEBA to connect the LSM synchronous motors see Servomotors order catalogue Matching motor e...

Page 29: ... and LSM with medium inertia Function DB15 male Plug of encoder cable Figure 3 13 2 The hiperface encoder diagram ServoA and LSM with medium inertia Function DB15 male Female plug Male plug Colour Figure 3 13 3 The resolver encoder diagram of ServoA and LSM with low inertia Function DB15 male Female plug Male plug Colour Figure 3 13 4 The hiperface encoder diagram of ServoA and LSM with low inerti...

Page 30: ...d Pin13 when using Hall TTL Sin Cos etc Compensation of power loss at connection of encoder SNS at Pin 13 condition same resistors in up and down line KTY Insulation characteristics as before that means control board without basic insulation Ready made up encoder cables The specifications can only be assured when using the KEBA system cables ELH2 EMM2 D15M R H xxx ELH2 applies to LSML EMM2 applies...

Page 31: ...TTL Signal B B B 7 8 GND GND GND GND GND 9 MTEMP GND PTC Klixon KTY MTEMP GND PTC Klixon KTY MTEMP GND PTC Klixon KTY MTEMP GND PTC Klixon KTY MTEMP GND PTC Klixon KTY 10 MTEMP PTC Klixon KTY MTEMP PTC Klixon KTY MTEMP PTC Klixon KTY MTEMP PTC Klixon KTY MTEMP PTC Klixon KTY 11 HALL_B B Position V TTL Signal B B B 12 13 SNS SNS SNS SNS SNS 14 R Position W TTL Signal NP R R 15 HALL_C R Position W T...

Page 32: ...ect with X4a 10 10 TEMP PTC KTY Klixon internal connect with X4a 10 TEMP PTC KTY Klixon internal connect with X4a 10 TEMP PTC KTY Klixon internal connect with X4a 10 TEMP PTC KTY Klixon internal connect with X4a 10 TEMP PTC KTY Klixon in ternal connect with X4a 10 11 B B B B 12 unconnected unconnected unconnected unconnected unconnected 13 SNS SNS SNS SNS SNS 14 R R R SCLK SCLK 15 R R R SCLK SCLK ...

Page 33: ... terminal configuration NOTE In the event of a short circuit or ground fault in the motor cable the power stage is disabled and an error message is issued NOTES The usage of encoders not included in the range supplied by KEBA requires special approval by KEBA X4a the maximun signal input frequency is 500kHz X4b the maximun signal input frequency is 2MHz for TTL only Encoders with a power supply of...

Page 34: ... 1 Connection to LSM motors For connection of the servomotor series LSM please use the ready made up motor cable Figure 3 14 1 Connection of motor for ServoA BG2 BG4 Figure 3 14 2 Connection of motor for ServoA BG5 ATTENTION DC linking of multiple drive controllers is not permitted ...

Page 35: ... in the corresponding application The drive controller is thermally designed in such a way that no energy input by the internal braking resistor is permitted during continuous operation with rated current and at maximum ambient temperature Consequently a controller design featuring an integrated braking resistor only makes Ready made up motor cable Order code PLH2 PMM2 xxxx xx xxx PLH2 applies to ...

Page 36: ...ults as dt i T I T eff 0 2 1 1 1 K I I P N eff DBr Br T PBr DBr dt P T P 0 1 T Br DBr PBr dt P P T 0 T P P T DBr PBr BrSum ATTENTION No additional external braking resistor may be connected to drive controllers with integrated braking resistor sense when the effective drive controller load is 80 or the braking resistor is de signed for one off emergency stop In the event of an emergency stop only ...

Page 37: ...eactivated and the connected drive controller is disconnected from the mains supply if the braking resistor overheats The minimum permissible connection resistance of the drive controller must not be infringed for technical data see chapter A 1 The braking resistor must be connected by a shielded cable Size BG2 BG4 Size BG5 Figure 3 15 1 Connection of braking resis tor for ServoA BG2 BG4 Figure 3 ...

Page 38: ... track A RS422 5 ES Z Encoder simulation track Z RS422 6 ME B Master encoder track B RS422 7 ME B Master encoder track B RS422 Open Collector 8 ES B Encoder simulation track B RS422 9 ES B Encoder simulation track B RS422 10 ES Z Encoder simulation track Z RS422 11 24V_GND Ground for 24V 12 24V Master encoder 24V supply max 200mA Identical voltage as digital I Os 13 ME COM Master encoder 24V suppl...

Page 39: ...A Operation Manual Electrical installation ID no LDS O SA EN 202103 Figure 3 20 Encoder simulation Figure 3 18 HTL 12V Signals Max Frequency is 200KHz Figure 3 19 Open collector signals Max Frequency is 200 KHz ...

Page 40: ...equirements EtherCAT System requirements KEBA devices Devices SAxx xxxx 0x34 0000 1 Standardisa tion IEC 61158 IEC 61784 2 IEC 61800 7 ESI file Current EtherCAT slave information ESI device description file for ServoA as xml file Is available with the firmware in the down load area at www keba com Table 3 10 System requirements KEBA devices System requirements KEBA devices Cable Patch cable from C...

Page 41: ...ction EC IN RJ 45 socket input EC OUT RJ 45 socket output Link Activity status Green LED Function Link Off No link No connection to another bus user On Link Connection to another bus user Activity L A Off No link No connection to another bus user On Link Connection to another bus user no activity Flashing Activity Data exchange active 3 14 1 6 Status Indicator The ERROR and the RUN indicator are c...

Page 42: ...nvalid configuration In case of an error indication the display shows alternating between RUN and ERROR indicator 3 14 1 7 EtherCAT axis Addressing Stations on EtherCAT are automatically addressed by their bus location The first drive on the network is axis 0 The second is axis 1 and so on ServoA EC OUT EC IN Control EC OUT ServoA EC OUT EC IN ServoA EC OUT EC IN Figure 3 23 EtherCAT connection ...

Page 43: ...b 9 pin female Wave terminating resistor Bus termination A jumper pin 1 2 activates the internal terminating resistor 120Ω Max input frequency 1 MHz Ext power supply Ext power supply SELV 12V 10 70mA 24V 20 30mA 3 14 2 1 Pin assignment of D Sub interface for CANopen communication interface 9 pin D Sub female on ServoA D Sub Pin Function 1 TR 2 CAN_LOW 3 CAN_GND 6 CAN_GND 7 CAN_HIGH 9 CAN_24V Figur...

Page 44: ...evice heats up in operation and at the heat sink may reach tem peratures of up to 100 C It poses a risk of skin burns if touched Cooling air must be able to flow through the device without restriction 4 2 Integrated KeyPad ServoA with integrated KeyPad KeyPad is located on top of the drive It is made up of 6 bit 7 segment LED and four function button You can use KeyPad to set parameter monitor ope...

Page 45: ... at the same time Save parameter When display menu Press T2 and T3 at the same time hold about 3s then store all parameter to EEPROM flash on the KeyPad Table 4 1 The function of T1 to T4 button 4 2 2 Parameter group overview ACT 1 Actual value APPL 2 User application PARA CONF 3 Device configuration CAM 4 CAM gear CTRL 5 Control settings ENC 6 Encoder AL 7 Error messages IN 8 Control inputs DISP ...

Page 46: ...ing preset of process sets via PLC control via terminal 12 Speed control reference and control via PLC 13 Positioning preset of process sets and cotrol via PLC 14 Speed control fixed speeds control via CAN Bus 15 Speed control reference and control via CAN Bus 16 Speed control reference via PLC control via CAN Bus 17 Positioning preset of process sets and control via CAN Bus 18 Positioning table p...

Page 47: ...Hall sensor 4 3 2 Select motor type P145 value Function description 0 User defined 1 Reserved 2 Reserved 3 Reserved 4 LSML06 020 2F xxx 5 LSML06 040 2F xxx 6 LSML08 075 2F xxx 7 LSML08 100 2F xxx 8 LSMM13 100 2N xxx 9 LSMM13 100 4N xxx 10 LSMM13 150 2N xxx 11 LSMM13 150 4N xxx 12 LSMM13 200 2N xxx 13 LSMM13 200 4N xxx 14 LSMM13 300 4N xxx 15 LSML08 075 4F xxx 16 LSML08 100 4F xxx ...

Page 48: ...5 Jog mode Manual mode Note Before Jog you should activate ENPO on X8 interface From the motor shaft Positive value of the speed indicate that the motor is running clockwise negative value of the speed indicate that the motor is running counterclockwise If the motor can not run or the direction is wrong or the value of the speed is wrong please check the mo tor cable and the encoder cable ...

Page 49: ...ation Manual Commissioning ID no LDS O SA EN 202103 4 4 Error messages Parameter No Function description Time between switching on and last error Last error Last but one error Last but two error Last but three error ...

Page 50: ...der if this error occurs again 17 Error in program memory detected during self test 1 Switch off on device 2 Please contact your service provider if this error occurs again E OFF DC link voltage is too low 212 425V or this error is also set at normal power off 1 Rectify power failure of connect higer mains voltage 5 Diagnostics The device states and error displays are indicated on the internal ope...

Page 51: ...tact your service provider if this error occurs again 49 Same as above 50 Internal error while current overload monitoring 1 Switch off on device 2 Please contact your service provider if this error occurs again Display Software code Error number Error description E OV Voltage overload 1 Voltage overload due to 1 Braking chopper overload braked too long or too much 2 Mains poer overload Remedy 1 S...

Page 52: ...s again 133 Invalid sequence in internal macro state machine functionality 1 Switch off on device 2 Please contact your service provider if this error occurs again 253 C user stack overflow 1 Switch off on device 2 Please contact your service provider if this error occurs again Display Software code Error number Error description E OTI Overheating of driver 44 Overheating of power stage heat sink ...

Page 53: ...lay Software code Error number Error description E PAR 103 Error in initialization of current model Check and change setting of control and motor parameter motor data set e g power class of motor and device are too different 104 Error in initialization of current control Check and change setting of control parameters CCG and CCTLG 105 Error in initialization of speed calculation Check and change s...

Page 54: ...nd encoder evaluation encoder lines or gear ratio not supported Check and change setting of encoder ECNO1 ECDE1 ECLN1 and SSI 118 Error in initialization of enccoder configuration not allowed combination of encoders e g using one encoder as rotary encoder and master encoder Check and change setting of encoder configuration CFSEC CFPEC CFREC CFX7 CFX2 119 Error in initialization of control nabsurb ...

Page 55: ... the faulty program line 2 Correct the process program resp faulty program line E SIO The USB interface communication error 4 No RS485 field bus available or baud rate invalid 9 Watchdog to control communication via LustBus actuated 1 connection 2 Check busmaster or increase parameter SWDGT 3 Switch off control factory setting via parameter SWDGT 0 Display Software code Error number Error descript...

Page 56: ...0mA detected or Motor phase failure detected 1 Broken wire at current input 4 to 20mA detected 1 Check contact of input 2 Check wiring 127 Motor phase failure detected 1 Check motor wiring 2 Check if power stage is enabled and safty stop not requested 3 Check motor coil for correct resistance Display Software code Error number Error description E BRC The internal chopper resistor is overloaded 0 T...

Page 57: ...ror error in frame check function Electronic Nameplate not available 196 ENP Write parameter error error during parameter access Please contact your service provider Display Software code Error number Error description E ENC 202 ENP error in process block 2 ECOFF Please contact your service provider 203 ENP error in process block 3 MotDatSM Please contact your service provider 204 ENP error in pro...

Page 58: ...limits Adjust reference value sent by master DIsplay Software code Error number Error description E HW Hardware limit alarm 51 Left hardware limit switch triggered 52 Right hardware limit switch triggered E HWE Hardware limit switch interchanged negative reference at positive limit switch or positive reference at negative limit switch 1 Correct wiring of limit switch or configure the inputs of dev...

Page 59: ...ider if this error occurs again Display Software code Error number Error description E ETC EtherCAT Bus Error 0 EtherCAT General Error Please contact your service partner for further information 20 EtherCAT General Error Please contact your service partner and check Parameter ECATS for further information 21 EtherCAT Watchdog 1 Process Data Communication interrupted 2 Check network cables or Maste...

Page 60: ...ly cancelled by an external command such as the On button or in KEBA controllers the ENPO 6 1 1 Overview of functional torque off connections ServoA offers a separate input for the torque off request a facility to deactivate the restart inhibit and a separate relay contact for feedback Des Term Specification Isolation Digital inputs ENPO X8 18 Disable restart inhibit torque off and enable power st...

Page 61: ... via two channels High H L H OFF OFF Power stage disabled via one channel Low L H H OFF OFF Power stage ready Low Previous status 1 3 x 106 switching cycles at 200 mA resting NO contact 2 n order to deactivate the restart inhibit the control signals must be simultaneously ENPO max 5ms before ISDSH set to High H or ISDSH must be reliably set to High H before ENPO 3 This only applies when functional...

Page 62: ... BG3 BG5 sizes ServoA Operation only within the technical ratings of the drive details see in technical ratings appendix A 3 ServoA technical data Multiple rated equipment of drive details see current capacity of ServoA in appendix A 1 Ensure that surrounding air temperature does not exceed the maximum approbate ambient temperature refer to model tables listed below Suitable For Use On A Circuit C...

Page 63: ... 1x15A 250V RK5 40 C 8kHz UL listed SA52 0150 3x230V 1x230V 5KA RMS 240V 5 7 lb in 1x20A 250V RK5 40 C 8kHz UL listed SA54 0100 3x400V 5KA RMS 415V 5 7 lb in 3x10A 600V RK5 40 C 8kHz UL listed SA54 0150 3x400V 5KA RMS 415V 5 7 lb in 3x15A 600V RK5 40 C 8kHz UL listed BG4 SA54 0200 3x400V 5KA RMS 415V 4 4 5 3 lb in 7 lb in 3x15A 600V RK5 40 C 8kHz UL listed SA54 0300 3x400V 5KA RMS 415V 4 4 5 3 lb ...

Page 64: ...6 16 2 30 0 5 3 230 3 16 2 30 0 5 SA52 0100 1 230 10 4 4 0 30 0 05 3 230 8 5 4 6 5 30 0 05 1 230 8 8 3 30 0 05 3 230 7 8 5 30 0 05 SA52 0100 1 230 8 16 3 30 0 05 3 230 7 16 5 30 0 05 SA52 0150 1 230 12 8 4 5 30 0 05 3 230 10 2 4 8 2 30 0 05 1 230 12 8 8 5 30 0 05 3 230 8 5 8 7 2 30 0 05 1 230 12 8 16 5 30 0 05 3 230 7 5 16 6 1 30 0 05 Data applies to motor cable length 10 m Maximum permissible mot...

Page 65: ...th 30 m All current ratings with recommended line reactor Table A 2 Rated current and overload time BG2 to BG5 3 x 400 V AC ServoA for 480 V Device Input Current Switching frequency of power stage Rated current 200 over load time 300 over load time IIN Aeff kHz IN Aeff s s SA54 0500 12 4 11 30 0 1 11 8 10 30 0 1 9 16 7 5 30 0 1 SA54 0750 14 4 16 30 0 5 14 8 16 30 0 5 7 16 6 30 0 5 SA54 0900 17 4 2...

Page 66: ...ive humidity may only be max 40 2 The absolute humidity is limited to max 29 g m So the maximum values for temperature and relative air humidity stipula ted in the table must not occur simultaneously 3 The absolute humidity is limited to max 25 g m That means that the maximum values for temperature and relative air humidity stipulated in the table must not occur simultaneously Table A 4 ServoA cli...

Page 67: ... 20 Input current 8 0A 1ph 3 3A 3ph 8 0A 1ph 7 0A 3ph 12 8A 1ph 8 5A 3ph 2 4A 3 0A 4 9A 6 0A 8 5A 14A 20A 25A Fluctuation of frequency 10 Asymmetryof mains supply 3 Control supply Voltage 24V DC Fluctuation of voltage 10 Fluctuation of frequency 5 Over capacity 2 In 30s 3 In 0 5s 2 In 30s 3 In 0 05s 2 In 30s 3 In 0 05s 2 In 30s 3 In 0 5s 2 In 30s 3 In 0 08s 2 In 30s 3 In 0 08s 2 In 30s 3 In 0 5s 2...

Page 68: ...68 ServoA Operation Manual ID no LDS O SA EN 202103 Appendix Space for your own notes ...

Page 69: ...69 ServoA Operation Manual ID no LDS O SA EN 202103 ...

Page 70: ...MAKE TECHNICAL CHANGES The content of our documentation was compiled with the greatest care and attention and based on the latest information available to us We should nevertheless point out that this document cannot always beupdated in line with ongoing technical developments in our products Information and specifications may be subject to change at any time For information on the latest version ...

Reviews: