43
ServoA
Operation Manual
Electrical installation
ID no.: LDS-O-SA-EN-202103
3.14.2 CANopen communication interface
The CANopen interface is integrated into the drive controller. The connection is made via
connector X5. The power for the electrically isolated connection is to be provided by the
customer.
Connection
Miniature D-Sub 9-pin female
Wave terminating resistor
- Bus termination -
A jumper (pin 1-2) activates the internal terminating resistor (120
Ω)
Max. input frequency
1 MHz
Ext. power supply
Ext. power supply (SELV) : 12V -10%, 70mA; 24V +20%, 30mA
3.14.2.1 Pin assignment of D-Sub interface for CANopen communication
interface
9-pin D-Sub female on ServoA
D-Sub
Pin
Function
1
TR
2
CAN_LOW
3
CAN_GND
6
CAN_GND
7
CAN_HIGH
9
CAN_24V
Figure 3.24 Pin assignment of D-Sub interface
543
21
98
76
Resolver
X5
Figure 3.25 Connection for CANopen communication interface