GB - 23
The CP-parameters form a selection of parameters defined by KEB. To
achieve access to the entire parameter range you require an application
manual.
Display
Parameter
Adjust. range
Resolution
Factory setting
CP. 0
Password input
0...9999
1
-
CP. 1
Actual frequency display
-
0,1 Hz
-
CP. 2
Inverter status display
-
-
-
CP. 3
Actual load
-
1 %
-
CP. 4
Peak load
-
1 %
-
CP. 5
Rated frequency
0...409.58 Hz
0.0125 Hz
50.0 Hz
CP. 6
Boost
0...25.5 %
0.1 %
2 %
CP. 7
Acceleration time
0.01...300 s
0.01 s
10 s
CP. 8
Deceleration time
0.01...300 s
0.01 s
10 s
CP. 9
Minimal frequency
0...409.58 Hz
0.0125 Hz
0 Hz
CP.10
Maximal frequency
0...409.58 Hz
0.0125 Hz
70 Hz
CP.11
Fixed frequency 1
0...±409.58 Hz
0.0125 Hz
5 Hz
CP.12
Fixed frequency 2
0...±409.58 Hz
0.0125 Hz
50 Hz
CP.13
Fixed frequency 3
0...±409.58 Hz
0.0125 Hz
70 Hz
CP.14
Max. ramp current
10...200 %
1 %
140 %
CP.15
Max. constant current
10...200 %
1 %
200 %
CP.16
Speed search
0...15
1
8
CP.17
Voltage stabilization
150...649 V,off
1 V
off
CP.18
Slip compensation
-2.50...2.50
0.01
0=off
CP.19
Autoboost
-2.50...2.50
0.01
0=off
CP.20
DC-braking
0...9
1
7
CP.21
Braking time
0...100 s
0.01 s
10 s
CP.22
Relay output
0...xx
1
2
CP.23
Frequency value
0...409.58 Hz
0.0125 Hz
4 Hz
CP.24
Reference signal (only C)
0...2
1
0
Operating of the unit
5.2
Parameter Summary
Password
FUNC
ENTER
UP
Releasing the
CP-Parameter
FUNC
ENTER
UP
Password
Barring the
CP-Parameter
5.3
Password Input
Ex works the frequency inverter is supplied without password protection, this
means that all changeable parameters can be adjusted. After parameterizing
the unit can be barred against unauthorized access. The adjusted mode is stored.