GB - 20
4.2.2
Connection of the Control
In order to prevent a malfunction caused by interference voltage supply on the
control inputs, the following directions should be observed:
- Use shielded/drilled cables
- Lay shield on one side of the inverter onto earth potential
- Lay control and power cable separately (about 10...20 cm apart)
- Lay crossings in a right angle (in case it cannot be prevented)
4.2.3
Digital inputs
Internal voltage supply
External voltage supply
4.2.4
Analog inputs
Internal analog set-point setting
External analog set-point setting
4.2.5
Outouts
When using inductive consumers at the relay output a protective wiring (i.e. free
wheeling diode) is necessary to protect the relay!
Installation
4
5
11 12 13 14
PE
4
6
12 13 14
PE
+
5
13...30 V DC
7
8
9
PE
8
9
+
-
SPS
PE
1
2
3
9 10
+
PE
Analog output:
0...10VDC / max. 5mA at
Ri
≥
56 K
Ω
const.
0...1mADC at
Ri
≤
5 k
Ω
const.
30 V DC/1 A
R = 3...10 k
Ω
0...±10 V DC
Ri = 40 k
Ω
EMC