GB - 39
Annex
Storage period < 1 year
•
Start-up without special measures
Storage period 1…2 years
•
Operate frequency inverter one hour without modulation
Storage period 2…3 years
•
Remove all cables from the power circuit; especially of braking resistor or module
•
Open control release
•
Connect variable transformer to inverter input
•
Increase variable transformer slowly to indicated input voltage (>1 min) and remain at
least on the specified time.
Voltage class
Input voltage
Residence time
400 V
0…280 V
15 min
280…400 V
15 min
400…500 V
1 h
Storage period > 3 years
•
Input voltages as before, however double the times per year. Eventually change capaci-
tors.
After expiration of this start-up the KEB COMBIVERT can be operated on nominal rating con-
ditions or delivered to a new storage.