GB - 34
Parameter Description
CP.27 Response
Description
2
Quick stopping,
holding torque,
restart after reset
Status message A.xx
Fast stop - holding torque on reaching 0 Hz. Correct the
error for the restart and activate reset. The drive remains
in condition fast stop until a reset signal is recognized.
3
modulation off,
automatic restart
Status message A.xx
Immediate switch off of modulation; the drive returns
automatically to normal operation, as soon as the fault
no longer exists.
4
Quick stopping,
modulation off,
automatic restart
Status message A.xx
Fast stop - switch off of modulation after reaching 0 Hz.
the drive returns automatically to normal operation, as
soon as the fault no longer exists.
5
Quick stopping,
holding torque,
automatic restart
Status message A.xx
Fast stop - holding torque on reaching 0 Hz. the drive
returns automatically to normal operation, as soon as
the fault no longer exists.
6
Warning signal by digital
output,
no message
No effect on the drive. Error is being ignored. Switching
conditions (CP.32 and CP.33) value „10“ are set.
CP.28 Motor protection / mode
The cooling mode of the motor is adjusted with these programmable parameters.
Value Condition
0
Motor with separate cooling
1
Motor with self-cooling
For self-ventilated motors the tripping times decrease with the frequency of the motor. The
motor protective function acts integrating, i.e. times with overload on the motor are added,
times with underload are substracted. After triggering the motor protective function, the new
tripping time is reduced to 1/4 of the specified value, if the motor has not been operated for
an appropriate time with underload.
CP.29 Motor protection / rated current
This parameter specifies the rated current (= 100% utilization) for the motor protective func
-
tion. The motor protection-load is calculated as follows:
Inverter apparent current (CP.04)
Motor protection load = –––––––––––––––––––––––––––––––
Motor protection / rated current (CP.29)
CP.30 Analog output 1 / Function
CP.30 defines the function of analog output 1. The output at the analog output is always made
in a range of 0…+10 V. Negative values are inverted and the output is displayed in a positive
value.
Value Function
Scaling factor
0…100 % (0…±100 %)
0
Absolute actual frequency CP.01
0…100 Hz
1
absolute set frequency CP.02
0…100 Hz
2
actual frequency CP.01
0…±100 Hz
3
set frequency CP. 02
0…±100 Hz
4
output voltage CP.09
0…500 V
Summary of Contents for COMBIVERT G6 series
Page 1: ...C O M B I V E R T Mat No Rev 00G6NEM DC00 1G GB Installation Manual Housing C Power 5 5 11kW...
Page 2: ......
Page 4: ...GB 4 Table of Contents...
Page 37: ...GB 37 Parameter Description...
Page 41: ...GB 41 Notes...