4.1 Overload characteristic
Characteristic 1
Characteristic 2
Time in s
30
60
90
120
150
180
210
240
270
300
0
105 110 115 120 125 130 135 140 145 150 160 170 180 190 200 210 220
Time in s
30
60
90
120
150
180
210
240
270
300
0
105 110 115 120 125 130 135 140 145 150
Load in %
Load in %
The characteristic declines device-dependently in this range.
Figure 1:
Overload characteristic
On exceeding a load of 105% the overload integrator starts. When falling below the
integrator counts backwards. If the integrator achieves the overload characteristic that
corresponds to the drive converter, the error E.OL is triggered.
4.2 Accessories
4.2.1
AIC, LCL and EMC filters
The line-side AIC or LCL filters are required for the characteristic of sinusoidal currents.
They filter the switching frequency of the drive converter. The basic assembly consists
of two inductors and capacitors (LCL filter). An EMC filter is additionally integrated at the
AIC filters.
Size
Housing
Cooling
AIC / LCL filters
EMC filter
Material number
f
SN
kHz
I
N
A
Material number
I
N
A
14
E
Air
14H6J4E-1000
8
16.5
integrated
–
16
G
Air
19H6J4E-1000
8
36
integrated
–
18
H
Air
19H6J4F-1000
8
60
integrated
–
20
1)
R
Air
19H6J4F-1000
8
60
integrated
–
20
R
Air
21H6J4F-1001
8
90
integrated
–
22
1)
R
Air/water
24H6J4F-1000
8
108
integrated
–
24
U
Air/water
24H6J4G-1000
8
180
integrated
–
26
U
Air/water
26Z1K04-1000
4-16
250
26E4T60-1001
300
27
1)
U
Water
26Z1K04-1000
8-16
275
26E4T60-1001
300
29
P
Water
29Z1K04-A000
4
460
30U5A0W-3000
650
Table 8:
AIC, LCL and EMC filters
1)
LCL filter limits the AIC current.
30
UNIT DATA
Summary of Contents for COMBIVERT F5 Series
Page 2: ......