10.1.5.2 Connection scheme for a cooling circuit (series connection)
Coolant connection for a master / slave system
F5/F6
Master
F5/F6
Slave
Coolant outlet
Coolant inlet
Coolant connection for a master / slave / slave system
F5/F6
Master
F5/F6
Slave 2
F5/F6
Slave 1
Coolant outlet
Coolant inlet
Figure 28:
Coolant connection
This connection scheme is only an installation proposal and does not replace
professional planning and execution!
If the drive converter system operates at rated operation, the coolant circuit can be done
in a series connection. It should be noted that the temperature is analog measured in the
slave modules and an error signal is given digitally to the master. The water return flow
should always be attached at the master in order to display real temperatures.
The heat power dissipation for each device size can be found in the technical data. The
resulting volume flow has to be in the recommended operating range of the temperature
difference (=>
„Volume flow in dependence of the heat power dissipation and tempera
). The relationships between heat power dissipation, flow and temperature
„Volume flow in dependence of the heat power dissipation and temperature
67
COOLING SySTEM
Summary of Contents for COMBIVERT F5 Series
Page 2: ......