Device size
30
33
34
38
Housing size
P
P
P
P
Cooling mode (L=air; W=water)
L
L
W
W
Number of modules for master/slave
2
3
2
3
Input data
Mains phases
3
Permitted mains forms
TN system
Rated input voltage
U
N
/ V
400
Input voltage range
U
in
/ V
340…480 ± 0%
Mains frequency
f
N
/ Hz
50 / 60 ± 2
Rated input power
S
N
/ kVA
395
554
616
1005
Rated input current
I
N
/ A
2 x 285
3 x 267
2 x 445
3 x 483
Max. permissible mains fuse type gR / aR
2 x 400
3 x 350
2 x 630
3 x 630
Output data
Rated output voltage
U
outN_dc
/ V
680
Output voltage range
2)
U
_dc
/ V
530...840
Overvoltage switch-off (E.OP)
U
OP_dc
/ V
840
Power supply/regenerative rated current
3)
I
outN_dc
/ A
570
800
890
1450
Max. regenerative DC current 30 s
I
out_max_dc
/ A
712
1000
1112
1813
Rated switching frequency
f
SN
/ kHz
4
5)
4
5)
4
5)
4
5)
Max. switching frequency
f
S_max
/ kHz
4
4
4
4
Other data (referring to the rated data)
Overcurrent cut-off (E.OC)
I
OC
/ %
150
150
150
150
Overload current (E.OL) 30 s
I
OL
/ %
125
125
125
125
Max. permissible DC link capacity
C
ext
/ mF
150
6)
250
6)
150
6)
250
6)
I
AIC
/ A
98
6)
145
6)
98
6)
146
6)
Max. external charging current (=>
I
ext
/ A
-
-
-
-
Max. permissible total charging current (=>
)
I
pre
/ A
98
6)
145
6)
98
6)
146
6)
)
Type
D1
Permissible DC fuses
Short-circuit factor at the connection point (
S
kn
/
S
N
)
10 <
S
kn
“ / < 350
Power dissipation at rated operation
P
BR
/ W
4700
6900
7400
12000
Max. heat sink temperature
t
_max
/ °C
90
7)
90
7)
90
7)
90
7)
1)
The input current of the
drive converter
must be limited to the rated current of the AIC / LCL filter, if
necessary.
2)
The operation is dependent on the voltage setpoint and the U
OP
3)
Measured at a reference voltage of 680 V DC.
4)
Limited by the rated current of the DC-terminal ! The input current must be limited to 300 A for input
voltages < 400 V.
5)
Must be set to 4 kHz for AIC operation (factory setting 2 kHz) !
6)
Option precharging resistor
„Additional precharging resistor at master-slave operation“
.
7)
Special settings are required for this device sizes (Reduction of the max. heat sink temperature
to 85°C,
=>
).
29