7.1.7 Relay outputs
In case of inductive load on the relay outputs a protective circuit must be provided (e.g.
free-wheeling diode)!
24 25 26
X2A
27 28 29
max. 30 V DC / 1 A
Figure 19: Relay outputs
7.1.8 Analog outputs
U
out
: 0...±10 V DC
I
max
: 10 mA
X2A
1 2 3 4 5 6 7 8 9
Figure 20: Analog outputs
7.1.9 Voltage output
The voltage output is used to control the digital inputs and for the supply of external
control elements. The maximum output current of 100 mA mA may not be exceeded.
10
18 19 20
X2A
21 22 23
+
-
ca. 24V DC / max. 100 mA
Figure 21: Voltage output
52