Device size
24
26
27
28
29
Housing size
U
U
U
P
P
Cooling mode (L=air; W=water)
L
L
W
L W
L
W
Number of modules for master/slave
–
–
–
–
–
–
Input data
Mains phases
3
Permitted mains forms
TN system
Rated input voltage
U
N
/ V
400
Input voltage range
U
in
/ V
340…480 ± 0%
Mains frequency
f
N
/ Hz
50 / 60 ± 2
Rated input power
S
N
/ kVA
125
173
208
256
319
Rated input current
I
N
/ A
180
250
300
1)
370
460
Max. permissible mains fuse type gR / aR
250
350
400
500
630
Output data
Rated output voltage
U
outN_dc
/ V
680
Output voltage range
2)
U
_dc
/ V
530…840
Overvoltage switch-off (E.OP)
U
OP_dc
/ V
840
Power supply/regenerative rated current
3)
I
outN_dc
/ A
180
250
300
4)
370
460
Max. regenerative DC current 30 s
I
out_max_dc
/ A 270
313
375
462
575
Rated switching frequency
f
SN
/ kHz
8
4
8
8
4
5)
4
5)
Max. switching frequency
f
S_max
/ kHz
8
8
8
8
4
4
Other data (referring to the rated data)
Overcurrent cut-off (E.OC)
I
OC
/ %
180
150
150
150
150
Overload current (E.OL) 30 s
I
OL
/ %
150
125
125
125
125
Max. permissible DC link capacity
C
ext
/ mF
45
43
40
35
35
)
I
AIC
/ A
226
226
226
98
98
Max. external charging current (=>
)
I
ext
/ A
–
–
–
–
Max. permissible total charging current (=>
)
I
pre
/ A
226
226
226
98
98
Type
D1
D1
Permissible DC fuses
=>
Short-circuit factor at the connection point (
S
kn
/
S
N
)
15 <
S
kn
“ / < 350
10 <
S
kn
“ /
< 350
Power dissipation at rated operation
P
BR
/ W
2230 2550 3500 4500
3000
3800
Max. heat sink temperature
t
_max
/ °C
90
90
60
90 60 90
6) 7)
90
6)
1)
The input current of the
drive converter
must be limited to the rated current of the AIC / LCL filter, if
necessary.
2)
The operation is dependent on the voltage setpoint and the U
OP
limit (=>
).
3)
Measured at a reference voltage of 680 V DC.
4)
Limited by the rated current of the DC-terminal ! The input current must be limited to 300 A for input
voltages < 400 V.
5)
Must be set to 4 kHz for AIC operation (factory setting 2 kHz) !
6)
Special settings are required for this device sizes (Reduction of the max. heat sink temperature to
85°C, =>
).
7)
Max. ambient temperature T
a
of 35°C.
28