NOTICE
The maximum temperature difference between pre-run and return flow
is specified in the technical data and should not be exceeded. If the vol
-
ume flow (above 30 l/min per module) is selected too large, increases
the risk of erosion in the liquid cooler.
10.1.5.3
Volume flow in dependence of the heat power dissipation and temperature difference
Pv
in kW
ΔT in K
0
1
2
3
4
5
6
7
8
9
10
11
12
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Legend
Master / Slave / Slave 9...12 ΔT in K
②
15 l/min
Master / Slave 6...10 ΔT in K
③
20 l/min
Master 3...6 ΔT in K
④
25 l/min
①
10 l/min
⑤
30 l/min
Figure 29: Volume flow in dependence of the heat power dissipation and temperature difference
68
COOLING SySTEM
Summary of Contents for COMBIVERT F5 Series
Page 2: ......