BATTERY
Rated DC Buss
Voltage
48 VDC
C
h
a
r
g
e
C
u
r
r
e
n
t
(
M
a
x
.
)
Charger Amps
7.
1
A
External
OPTIONAL TO 45 A
Recharge time (to90%)
BATTERY TYPE AND SIZE DEPENDANT, CHARGER DEPENDANT
Floating Mode
Charging Voltage
54.8Vdc
±
1
%
Bulk Mode Charging
Voltage
56.4Vdc
±
1
%
DC leakage current
30 µA with no AC applied and the unit in the off position
Transfer
Time
AC to DC
0 ms
Inverter to Bypass
0 ms (Typical)
DC start
Startup in battery mode
during a power failure
Yes
Self
Diagnostics
Upon Power-on, Front Panel Setting & Software Control, 24- hour routine check
Front Panel
LCD (Standard)
LCD(2) 4 line Timer
Normal, Battery, Bypass, Self-Test, Battery Weak & Bad, Site Wiring Fault , Fault,
Overload, and Load/Battery Level
Programable timer, 100 hr delay Battery Temp Probe, Low battery setting relay etc.
6 Button
ON(Silence) / OFF / Enter / Function / UP / Down
Audible
Alarms
Battery Mode
Sounds once every 1.5 seconds
Low Battery
Sounds once every 0.2 seconds
Overload
Sounds once every 3 seconds
Normal alarm
Sounds once every 3 seconds
Fault
Continuous tone
Protection
Short Circuit
Bypass mode : Breaker
Normal Mode : Output Breaker/Electronic Circuit Battery Mode :
Output Breaker/Electronic Circuit
Battery
Auto battery detection with internal fast blow fusing
EPO
UPS shuts down immediately N/C or NC option.
Over Temperature
Normal Mode :Transfer to Bypass Mode Battery Mode : UPS
shuts down immediately
42
DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English
20180312
- This manual is for qualified personnel only