DBL MX-U Specifications
MODEL
ITEM
MX
100
0U-
48
MX-1500U-48
MX-2000U-48
CAPACITY
VA
10
00VA
1500 VA
2000 VA
W
INPUT
Voltage Rating
1000 W
1500 W
18
00 W
55/75/90-150 VAC (Based on load percentage 0-60% / 0-75% / 0- 100%)
Frequency Rating
44Hz-66Hz Fin <44Hz
>56Hz-60Hz Fin <54Hz or Fin >66Hz
Phase
Single phase with ground
Power Factor
≧
0.99 at full linear load
Current harmonic
distortion (THDi)
<7% at full load and nominal voltage
Generator Input
Compatible with Generator Power
Input Connection
Terminal
OUTPUT
Voltage
120 V, adjustable to 100/110/115/120/127
Voltage Regulation
Static
:
within ±1% until low-battery warning
Frequency
(Synchronized
Range)
3 Hz or 1 Hz (selectable)
Frequency (Battery Mode)
50/60 Hz ±0.2% unless synchronized to line
Current Crest Ratio
3:1
Voltage Harmonic
Distortion(THDv)
< 3% at full linear load
< 7% at full non-linear load
Voltage Regulation
±1%
Dynamic Stability
≦
60ms/5% @ 10% to 90% Load
Output Waveform
Pure sine wave
Outlets
1x Terminal,
2
x
NEMA 5-15R
AC Inverter Supply
<
105
%
continuous
106-120
%
for 30 seconds transfer to bypass
121-150
%
for 10 seconds transfer to bypass
>
150
%
Immediately transfer to bypass.
Buzzer continuously alarms.
Line mode
>90%
Efficiency
Battery mode
>86%
ECO mode
>96%
Battery String Qty.
4
DC Connection
Anderson 4 p
ole
4
1
SECTION 15
DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English
20180312
- This manual is for qualified personnel only