SECTION 1
4
1
4
.1
TROUBLE SHOOTING
Quick REFERANCE Error Codes, These are the most common error codes that you may see with the UPS
installed. For a more comprehensive list please refer to SECTION 14.
CODE
RESULT
WHEN OCCURS
STATUS
ACTION
ER 02
RESERVED
Er 03
RESERVED
Er04
Inverter out of order
Initial backup
UPS is locked and shows the
error code & alarm.
When the
input voltage is out of
windows
(<80Vac to 135
)
Check and verify the AC input
connections. Check and verify the
Bypass connections Load ( RED)
Line ( BLACK).
Reconnect All AC connections.
Line
Displays error code & alarm,
switches to bypass mode
for 1
min., then switches back to
Inverter mode.
Check and verify the AC input
connections. Check and verify the
Bypass connections Load ( RED)
Line ( BLACK).
Reconnect All AC connections.
Verify that the load does not exceed
rated output of the UPS,
Er05
Battery weak or dead
battery
discharge-test
If the bat. Voltage measured
during self-test is
below
8nV(or 4mS) or
10.4nV(128ms), the self-test
will be ceased and the UPS
will switch back to Line
Mode
& show error code and alarm
Check and verify battery QTY.
Max
6
x 55AH without
ext
ABM.
How old are the batteries.
Has there been a power
failure? For faster recharge
install ABM.
backup
If the battery voltage drops to
8nV suddenly, the
backup UPS
will lock itself immediately and
show error
code & alarm.
Check and verify battery QTY.
Max
6
x 55AH without
ext
ABM.
How old are the batteries.
Has there been a power failure?
For faster recharge install ABM.
Before
discharge-test
If the battery voltage is lower
than 12.5nV, the UPS
will
cease the self-test right away
and show error
code & alarm.
Check and verify battery QTY.
Max
6
x 55AH without
ext
ABM.
How old are the batteries.
Has there been a power failure?
For faster recharge install ABM.
Er06
Inverter Short Circuit
Show error code & alarm.
Check and verify AC connections.
Red to Load, BLACK to Line.
Check load for short circuit.
No retry
If the UPS is set at not retry
the UPS will lock
directly and
show error code & alarm.
The UPS will shut down.
Check and verify AC connections.
Red to Load, BLACK to Line.
Check load for short circuit. Clear
the short and restart UPS.
CODE
RESULT
OCCURS
STATUS
ACTION
E
PO
EPO
Shuts Down the UPS
then shows an error
code.
EPO Locks the UPS
Remove the contact closure
applied to the UPS. Remove
AC power to the UPS, then
reconnect and restart the
system.
Er08
DC BUSS, Abnormal
high-voltage-level
initial or backup
Locks the UPS, then show
s
an error code & alarm
Remove all DC and AC
connections. Connect the
batteries, perform DC Cold-
Start, when UPS is operating
apply AC by connecting the
AC harness.
Line
Displays error code & alarm.
Switches to bypass for 1
minute then back to Inverter.
Remove all DC and AC
connections. Connect the
batteries, perform DC Cold-
37
DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English
20180312
- This manual
is for qualified
personnel only.